Installation, Clearances – Regency Horizon HZ30E Small Gas Fireplace User Manual

Page 10

background image

10

Regency Horizon™ HZ30E-1 Gas Fireplace

INSTALLATION

Caution Requirements

The top, back and sides of the fi replace are defi ned by

standoffs. The metal ends of the standoff may NOT be

recessed into combustible construction.

WARNING

Fire hazard is an extreme risk

if these clearances (air space) to combustible materials are not

adhered to. It is of greatest importance that this fi replace and vent

system be installed only in accordance with these instructions.

CLEARANCES

The clearances listed below are Minimum distances unless otherwise stated:

A major cause of chimney related fi res is failure to maintain required clearances (air space) to combustible materials. It is of the greatest importance
that this fi replace and vent system be installed only in accordance with these instructions.

F

E

D

A

Installed Close

to Floor

G

Clearance:

Dimension

Measured From:

A: Sidewall (on one side)

8" (203mm)

Side of Fireplace Opening

B: Ceiling
(room and/or alcove)

39" (991mm)

Top of Fireplace Opening

C: Mantel Height (min.)

13-1/4" (330mm)

Top of Fireplace Opening

D: Mantel Depth (max.)

12" (305mm)

21-1/4" Above Fireplace
Opening

E: Alcove Width

60" (1524mm)

Sidewall to Sidewall (Minimum)

F: Alcove Depth

36" (914mm)

Front to Back Wall (Maximum)

G: From Floor

21" (533mm)

Top of Fireplace Opening

Note:

0"

No hearth required

B

A

Flue Clearances to Combustibles

Horizontal - Top

3"

Horiztonal - Side

2"

Horiztonal - Bottom

2"

Vertical

2"

Passing through wall/
f l o o r / c e i l i n g - w h e n
fi restop is used.

1-1/2"

Alcove

Unit

E

F