Measurement specifications – SATEC SA300 ezPAC Installation Manual User Manual
Page 42

Appendix: Technical Specifications
39
Measurement Specifications
Accuracy
Parameter
Full Scale @
Input Range
%
Reading
% FS
Conditions
Range
Voltage V1-V4
120VxPT @
120V
400VxPT @
690V
0.2
0.01
10% to 120% FS
0 to 999,000 V
SA310, SA320
Line current I1-
I4
CT
0.2
0.2
0.2
0.01
0.01
ANSI C12.20:
1% - 120% FS
120% - 400% FS
IEC 687:
1% - 200% FS
0 to 9999 A
Fault current I1-
I4
CT
2.0
400% - 3000% FS
0 to 9999 A
SA330
Line current I5-
I8
CT
0.2
0.2
0.2
0.01
0.01
ANSI C12.20:
1% - 120% FS
120% - 400% FS
IEC 687:
1% - 200% FS
0 to 9999 A
DC Voltage
125V/220V
0.3
10% - 120%FS
0 to 290VDC
Active power
0.36
×PT×CT @
120V
1.2
×PT×CT @
690V
0.2
0.002
0.002
|PF|
≥ 0.5 and
c
-2,000,000 to +2,000,000 kW
Reactive power
0.36
×PT×CT @
120V
1.2
×PT×CT @
690V
0.3
0.002
0.002
|PF|
≤ 0.9 and
c
-2,000,000 to +2,000,000
kvar
Apparent power
0.36
×PT×CT @
120V
1.2
×PT×CT @
690V
0.2
0.002
0.002
|PF|
≥ 0.5 and
c
0 to 2,000,000 kVA
Power factor
1.000
0.35
|PF|
≥ 0.5,
I
≥ 2% FSI
-0.999 to +1.000
Frequency
0.02
40.00 Hz to 70.00 Hz
Total Harmonic
Distortion, THD
V (I), %Vf
(%If)
999.9 1.5
0.2
THD
≥ 1% FS,
V (I) ≥ 10% FSV
(FSI)
0 to 999.9
Total Demand
Distortion, TDD,
%
100
1.5
TDD
≥ 1% FS,
I
≥ 10% FSI
0 to 100
Active energy
Import & Export
Class 0.2 ANSI C12.20-1998
Current class 20
Class 0.2S (IEC 687-1992-6)
0 to 999,999.999 MWh
Reactive energy
Import & Export
Class 0.2 under conditions as per ANSI
C12.20-1998
Class 0.2 under conditions as per IEC 687-
1992-6
0 to 999,999.999 Mvarh
Apparent
energy
Class 0.2 under conditions as per ANSI
C12.20-1998
Class 0.2 under conditions as per IEC 687-
1992-6
0 to 999,999.999 MVAh
Volt-hours
Class
0.2
20%
- 120% FS
0 to 999,999.999 kVh
Ampere-hours
Class
0.2
10%
- 200% FS
0 to 999,999.999 kAh
Symmetrical
components
Voltage FS
Current FS
Current FS
1
1
3
10% - 120% FS
10% - 200% FS
200% - 3000%FS
Phasor angles
1 degree