beautypg.com

Plug-in i/o ratings – SATEC SA300 ezPAC Installation Manual User Manual

Page 37

background image

Appendix: Technical Specifications

34

Terminals Pitch: 9.5 mm

Standard AC Current Inputs: I1, I2, I3, I4

Input via CT with 5A secondary

Operating range: continuous 20A RMS (ANSI C12.20) or 10A RMS (IEC687)

Fault Currents: up to 150A RMS (30x)

Burden: < 0.15 VA

Overload Withstand: 20A RMS continuous, 250A for 1 second

Wire Size: 10 AWG (2.5 to 6 mm

2

)

Terminals Pitch: 13 mm

Input via CT with 1A secondary

Operating Range: continuous 4A RMS (ANSI C12.20) or 2A RMS (IEC687)

Fault Currents: up to 30A RMS

Burden: < 0.02 VA

Overload Withstand: 4A RMS continuous, 50A for 1 second

Wire Size: 10 AWG (2.5 to 6 mm

2

)

Terminals Pitch: 13 mm

Optional AC Current Inputs: I5, I6, I7, I8

Input via CT with 5A secondary

Operating Range: continuous 20A RMS (ANSI C12.20) or 10A RMS (IEC687)

Burden: < 0.15 VA

Overload Withstand: 20A RMS continuous, 250A for 1 second

Wire Size: 12 AWG (1.5 to 3.5 mm

2

)

Terminals Pitch: 10 mm

Input via CT with 1A secondary

Operating Range: continuous 4A RMS (ANSI C12.20) or 2A RMS (IEC687)

Burden: < 0.02 VA

Overload Withstand: 4A RMS continuous, 50A for 1 second

Wire Size: 12 AWG (1.5 to 3.5 mm

2

)

Terminals Pitch: 10 mm

VDC Voltage Input

Operating Range: 2-290 VDC

Burden: < 0.2 W

Accuracy:

±0.5%

Galvanic Isolation: 2500V DC

Wire Size: 10 AWG (up to 6 mm

2

)

Terminals Pitch: 9.5 mm

Scan time: 1/2 cycle

Plug-In I/O Ratings

Digital Inputs (up to 3 I/O Modules)

Scan time: 1 ms @ 60Hz, 1.25 ms @ 50Hz.

16-DI optically isolated, dry contact sensing (voltage-free):

Internal power supply 24 VDC

Sensitivity: open @ input resistance >100kOhm, closed @ input resistance <1kOhm

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 5 mm

16-DI optically isolated, wet contact sensing:

External Power Supply: 24 VDC

Sensitivity: open @ voltage<8 volts, closed @ voltage>17 volts

Wire Size: 12 AWG (up to 2.5 mm

2

)

Terminals Pitch: 5 mm