Appendix: Technical Specifications

37

Ethernet Port

Transformer-isolated 10Base-T port.

Connector Type: RJ45 modular.

Supported Protocols: Modbus TCP (Port 502), DNP 3.0/TCP (Port 20000). IEC61850 (including
GOOSE & MMS)

SNTP Time synchronization.

Number of simultaneous connections (sockets): 5.

Modem Port

Transformer-isolated internal 56K modem.

Connector Type: RJ11.

Supported Protocols: Modbus RTU/ASCII, DNP 3.0.

Infrared Port

Optional optical IEC/ANSII head.

Baud Rate: up to 115,200 bps.

Supported Protocols: Modbus RTU/ASCII, DNP 3.0.

Real-time Clock

Accuracy: maximum error 15 seconds per month @ 25

°

C

IRIG-B Port

Optically isolated IRIG-B port.

Time code signal: unmodulated (pulse-width coded).

Level: unbalanced 5V.

Connector Type: BNC.

Recommended cable: 51Ohm low loss - RG58A/U (Belden 8219 or equivalent), TNC connector.

Recommended GPS time code generator: Masterclock GPS-200A.

Log Memory

Standard onboard memory: 4 Mbytes.

Plug-in expansion memory module: 64/128 Mbytes

Remote Display Module

Display: high-brightness seven-segment digital LEDs, three 6-digit windows

Keypad: 6 push buttons

Communication: EIA RS-485 port with 12V supply voltage

Connector Type: captured-wire, 5 terminals

Wires Size: up to 12 AWG (up to 2.5 mm

2

)

Distance: up to 1200m (4000 feet)