OUtpUt terMiNaL paNeL CONNeCtiONs
uvWo terminal output voltages
Various output voltages can be obtained using the UVWO
output terminal lugs. The voltages at the terminals are
dependent on the placement of the jumpers plates (6) on
the
voltage change-over Board and the adjustment of
the
voltage regulator control Knob.
Remember the voltage change-over board determines the
range of the output voltage and can be configured in two
different positions that provide 6 different output voltages
at the UVWO output terminals. The generator is shipped
from the factory in the 240V configuration. The voltage
regulator (VR) allows the user to increase or decrease the
selected voltage.
3Ø-240v uvWo terminal output voltages
1. Jumper the voltage change-over board for 240V
operation as shown in Figure 19
Figure 19. Voltage Change-Over Board 240V
Configuration
2. Connect the load wires to the UVWO terminals as
shown in Figure 20.
Figure 20. UVWO Terminal Lugs
3. Turn the voltage regulator knob (Figure 21) clockwise
to increase voltage output, turn counterclockwise to
decrease voltage output. Use voltage regulator
adjustment knob whenever fine tuning of the output
voltage is required
Figure 21. Voltage Regulator Knob
1Ø-240v uvWo terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 19.
2. Connect the load wires to the UVWO terminals as
shown in Figure 21.
Figure 22. UVWO Terminal Lugs 1Ø-240V
Connections
1Ø-120v uvWo terminal output voltages
1. Make sure the voltage change-over board is jumpered
for 240V operation as shown in Figure 18.
2. Adjust voltage regulator knob (Figure 21) for an output
of 208V to obtain 120V at the UVWO terminals.
3. Connect the load wires to the UVWO terminals as
shown in Figure 23.
Figure 23. UVWO Terminal Lugs