beautypg.com

Output terminal panel familiarization, Output terminal panel, Output terminal familiarization – Multiquip DCA300SSCU2_SSCU4i User Manual

Page 20: Figure 6. output terminal panel

background image

page 20 — dca300sscu2/4i 60 hz generator • operation and parts manual — rev. #1 (10/21/13)

OUtpUt terMiNaL paNeL faMiLiariZatiON

output terminal panel

The Output Terminal Panel (Figure 6) shown below is

located on the right-hand side (left from control panel) of

the generator. Lift up on the cover to gain access to

receptacles and terminal lugs.

NOTICE

Terminal legs “O” and “Ground” are considered bonded

grounds

output terminal Familiarization

The “Output Terminal Panel ” (Figure 7) is provided with

the following:

„

Three (3) 240/139V output receptacles @ 50 amp

„

Three (3) Circuit Breakers @ 50 amps

„

Two (2) 120V GFCI receptacles @ 20 amp

„

Two (2) GFCI Circuit Breakers @ 20 amps

„

Eight (8) Output Terminal Lugs ( U, V, W, O, Ground)

300

U

V

W

O

GND

AUX. POWER RECEPTACLES

240/139V, 50 AMPS

O

U

V

W

1Ø AND 3Ø,

480 -120 VAC

OUTPUT TERMINALS

NEUTRAL

TERMINAL

GROUND

TERMINAL

HARD WIRE

HOOKUP PANEL

BLACK

RED

BLUE

WHITE

GREEN

120 VAC, 20 AMP

GFCI RECEPTACLES

Y

X

W

CS-6369

TWIST-LOCK

CIRCUIT BREAKERS
FOR CS-6369 TWIST

LOCK RECEPTACLES

CIRCUIT BREAKERS

FOR GFCI RECEPTACLES

Figure 6. Output Terminal Panel