Mechanically attached metal roof panels - Type “Image II”

For use in Design Nos. P224 , P225 , P227 , P230 , P237 , P508 , P510 , P512 , P701 , P711 , P712

, P713 , P715 , P717 , P720 , P722 , P723 , P724 , P726 , P731 , P734 , P736 , P803 , P814 , P815 ,

P818 , P819 , P821 , P823 , P824 .

*Hat shaped member to be a minimum of 16 gauge. The member will be fastened through the roof

insulation to the steel roof deck with min. No. 14 self-drilling and/or self-tapping fasteners. Spacing

to be determined by the structural loading requirements. In addition any compressible UL Classified

glass fiber blanket insulation with or without a vapor retarder facing may be used between the speci-

fied roof insulation and the metal roof panels.

**Bearing plate to be a minimum of 16 gauge. Member will be fastened through the roof insulation to

the steel deck with min. No. 14 self-drilling and/or self-tapping fasteners.

See the UL Fire Resistance Directory for explanation of each design number listed above.

Metal Roof Deck Panels

Metal Sales Manufacturing Corporation has obtained fire resistance ratings for various products

conducted according to test criteria set forth by 'Underwriters Laboratories' "Standard Fire Tests

of Building Construction and Material" (ANSI/UL 263). This test procedure is identical to ASTM

E-119 and NFPA 251.

The fire resistance rating is for the total assembly and not just the external metal panel. Ratings

are expressed in hours and vary depending upon the assemblies.

In general, the test criteria is to evaluate the assembly's ability to continue to support the super-

imposed loads and resist the passage of flame, high temperatures, or hot gases which will ignite

combustible materials. The test assemblies are identified by an alpha-numeric design number.

For detail information on specific assemblies and hourly ratings see UL Fire Resistance Direc-

tory.

Underwriters Laboratories Inc.

®

UL

®

LISTED