Electrical installation
Wiring for the operation of inputs and outputs
6
l
52
EDBMZ9374X DE/EN/FR 4.2
6
Electrical installation
6.1
Wiring for the operation of inputs and outputs
ƒ
The wiring is required for the versions:
–
33.9374IB.0B.01, 33.9374IB.0C.02, 33.9374IB.0C.05
GND
I/O1 I/O2 I/O3 I/O4 I/O5 I/O6
GND
I/O7
LO
I/O8
HI
mC
- +
GND
24V
OUT
24V
1
2
3
4
5
0 ~
–
PE
9374_013
0
Power supply with +24 VDC output voltage
l
When dimensioning the power supply take into account the currents at the
outputs (max. 1 A per output).
1
Emergency switch
l
It must be ensured that the outputs do not carry any voltage and the inputs do
not receive a HIGH signal when the switch is actuated.
2
Digital inputs with normally−open contact
3
Digital outputs with consumer
4
System bus (CAN) (
^
5
PE connection (6.3 mm AMP connector)
l
Connect the PE connection with the conductive rear panel of the control
cabinet. This ensures a troublefree operation of the terminal extension.
{
Danger!
Install an additional mains isolation if
ƒ
the terminal extension is connected to a host,
ƒ
a safe mains isolation (double insulating distance) according to
EN 50178 is necessary.