beautypg.com

Connecting the mains voltage – Lenze EMF2133IB User Manual

Page 64

background image

5

Commissioning

Connecting the mains voltage

EDKMF2133 DE/EN/FR 6.1

64

l

H2 NetzspgZuschalten−unkontroll Anlauf

Connecting the mains voltage

)

Note!

If you use the external voltage supply for the communication module, please
switch it on.

The following LEDs at the front of the communication module must be on:
ƒ The top green LED: "Status display for voltage supply"
ƒ The bottom green LED: "Status display for drive"

Protection against uncontrolled restart

)

Note!

In some cases the controller should not restart after a fault (e.g. after a short
mains failure).

ƒ

The drive can be inhibited by setting C0142 = 0 if
– the corresponding controller sets a "LU message" fault and
– the fault is active for more than 0.5 seconds.

Parameter function:

ƒ

C0142 = 0
– The controller remains inhibited even after the fault has been

eliminated and

– the drive restarts in a controlled mode: LOW−HIGH transition at terminal

28 (CINH)

ƒ

C0142 = 1
– An uncontrolled restart of the controller is possible.