Electrical installation – Lenze E84AZESR Mains filter-RFI filter 42-96A User Manual
Page 48

Electrical installation
Important notes
l
48
EDK84AZESxx DE/EN/FR/ES/IT 4.0
(
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains
fluctuations and voltage peaks.
(
Stop!
Dangerously high temperatures
The filter is not protected against mains phase failure. In the event
of a mains phase failure, the filter may become very hot.
Possible consequences:
ƒ
Destruction of the device.
ƒ
Smouldering or open fire.
Protective measures:
ƒ
Change the setting for code C00565 from "Warning" to "Fault" or
ƒ
select a wiring for the bMctrlMainsFault status output
(LS_DeviceMonitor) system block which causes the system to
shutdown within one minute if said output is set to HIGH.