beautypg.com

JUMO 706030 LOGOPRINT 500 Printing Recorder Data Sheet User Manual

Page 10

background image

2013-01-29/00355277

Data Sheet 706030

JUMO GmbH & Co. KG • 36035 Fulda, Germany

Page 10/12

Overview of the electrical isolation

Inputs/outputs

Connector

Diagram

ER8 external relay module

Communication
with external
relay module

Voltage source for external
2-wire transmitter

24V 45mA ± 5%

7.

Logic operating inputs

min. pulse length:
HIGH 400msec
LOW 400msec

Contact operation
LOW = R

OFF

 100k

HIGH = R

ON

 50

Voltage operation
LOW = 0 — 5V DC
(inactive)
HIGH = 20 — 35V DC
(active)

contact no. 7 = logic input 1

.

.

.

contact no. 14 = logic input 8

Open-collector outputs

DOUT1 — DOUT4
U

max

= 32V DC

I

max

= 100mA

Residual voltage DOUT
active
U

DOUTactive

=

0.4 — 1.2V

8.

RS422/RS485 serial interface

Communication
with higher-level
systems

9.