6 instrument description – JUMO 60.3031 Surface-mounting thermostats, ATH.-SE Operating Manual User Manual

Page 21

background image

21

6 Instrument description

Operating
mode

as per EN 60 730-1

TW:

Type 2BL = automatic mode

with microswitch disconnection in operation,
which requires no auxiliary energy source.

STB, STW (STB): Type 2BK = automatic mode

with microswitch disconnection in operation,
with fail-safe facility.

Operating position

unrestricted (with open-air mounting on request)

Weight

approx. 0.65 kg

Capillary and
probe materials

Minimum
bending radius

5 mm

Switching point
accuracy

(in % of scale range;
in relation to the set point or limit value at +22 °C ambient temperature)

TW

in upper third of scale

±

1.5%

at start of scale

±

1.5%

STB, STW (STB)

in upper third of scale

at start of scale

Mean ambient
temperature
influence

(in % of scale range) in relation to the limit value

There is a displacement of the switching point if the ambient temperature at
the thermostat head and/or the capillary deviates from the +22 °C calibration
ambient temperature.
higher ambient temperature = lower switching point
lower ambient temperature = higher switching point

End of scale

Capillary

Probe

up to +200 °C copper Mat. Ref. 2.0090

tin-plated, 1.5 mm dia.

copper Mat. Ref. 2.0090
tin-plated, brazed

up to +300 °C copper Mat. Ref. 2.0090

tin-plated, 1.5 mm dia.

stainless steel
Mat. Ref. 1.4571, brazed

up to +500 °C stainless steel,

1.5 mm dia.

stainless steel
Mat. Ref. 1.4571, welded

+0

-5

%

+0

-10

%

for temperatures with end of scale:

below +200 °C

+200 °C to +350 °C

TW

STB/STW (STB)

TW

STB/STW (STB)

influence on thermostat head, % per °C

0.08

0.17

0.06

0.13

influence on capillary, % per °C per m length

0.047

0.054

0.09

0.11