5 Settings

5.2

Resetting the STB

After the temperature has fallen below the set limit value (safe temperature
limit) by about 10% of the scale range, the microswitch can be reset.

Action

5.3

Self-monitoring

5.3.1

Behaviour in the event of a measuring system breakage

5.3.2

Response to low temperature

5.4

Using the STW(STB) as STB

1.

2.

3.

✱ Unscrew the cap nut

(1).

✱ Press the reset but-

ton (2) until the micro
switch is reset.

✱ Screw the cap nut (1)

back on

H

On the STB and STW (STB), the circuit stays open permanently in the event of
a measuring system breakage (leakage).

On the STB, the microswitch is additionally locked.

H

If the probe temperature goes below the minimum value of -10 °C, the circuit is
opened.

After the minimum probe temperature is exceeded, the STB must be manually
reset.
➈ Section 5.2 “Resetting the STB”, page 19.
The TW and STW reset automatically.

V

The restart lock as per DIN EN 14597 must be ensured by the subsequent cir-
cuit. This circuit must be in accordance with VDE 0116.