6 Instrument description

6.1

Technical data

Permissible
ambient
temperature
in operation

Permissible
overtempera-
ture safety

on the probe during use

max. scale end value +15%

Permissible
storage
temperature

maximum +50 °C, minimum -50 °C

Case

Cover: aluminium die casting with screws for lead sealing

Base: die-cast aluminium, painted

Connection
cable

Diameter 10 — 16.5 mm, maximum conductor cross-section 2.5 mm

2

Switching
differential
in % of
limit value
range

Max.contact
rating

Fusing required

see contact rating

Protection

IP54 as per EN 60 529, operation under normal conditions

Operating
medium

Water, oil, air, superheated steam

Time constants
t

0.632

Capillary

Thermostat head

with scale limit value

maximum

+80 °C

+80 °C

minimum

-40 °C

-40 °C

below +200°C

-20 °C

-20 °C

> 200 °C to < 350 °C

Code

only on types 2 and 20

nominal value

possible actual value

S 1
S 2
S 3

3
6

1.5

3 - 4
6 - 8
1 - 2

TW, STW (STB) with hysteresis 3% and 6%

230 V, 10 (2) A AC, p.f. = 1 (0.6)

230 V, 0.25 A DC

TW, STW (STB) with hysteresis 1.5%

230 V, 6 (1.2) A AC, p.f.

= 1 (0.6)

in water

in oil

in air / superheated steam

< 45 sec.

< 60 sec.

< 120 sec.