beautypg.com

2 binary inputs/outputs (option), 3 outputs, 4 interfaces – JUMO 706585 LOGOSCREEN fd Recorder with stainless steel front Installation Instructions User Manual

Page 36: Binary inputs/outputs (option), Outputs, Interfaces, 6 technical data (extract from data sheet)

background image

6 Technical data (extract from data sheet)

36

6.2 Binary inputs/outputs (option)

6.3 Outputs

6.4 Interfaces

Input or output

configurable as input or output

Number

8, 16 or 24, depending on the device version,
to DIN VDE 0411, Part 500; max. 25 Hz, max. 32 V

Input

level

logic "0": -3 to +5 V (input current max. ±1 mA),
logic "1": 12 to 30 V (2.5 mA

 input current  5 mA)

counting frequency

8Hz

High-speed input

the first two binary inputs of each module (B1, B2, B9, B10, B17, B18),
if the module is not fitted with relays or 6 analog inputs

task

count function, e.g. for flow measurement

counting frequency

10 kHz

Output

type

open-collector output, switches relative to positive voltage

level

logic "0": transistor is inhibited
(max. permissible voltage across switching transistor 30 V,
max. leakage current 0.1 mA)
logic "1": transistor is switched on
(max. voltage across switching transistor 1.6 V, max. current 50 mA)

sampling cycle

at least 1 sec (1 Hz)

1 relay (ex-factory)

changeover (SPDT), 3 A, 230 V AC

a

a

With resistive load.

6 relays (option)

changeover (SPDT), 3 A, 230 V AC

a, b

b

It is not permissible to mix SELV circuits and supply circuits.

RS232/RS485 (connector 7)

Qty. 1, switchable between RS232 and RS485

protocol

Modbus master, Modbus slave and barcode reader

baud rate

9600, 19200, 38400

modem

can be connected

connector

SUB-D

external inputs

via the Modbus master/slave function, 24 analog and 24 binary

RS232 for barcode reader
(connector 2)

Qty. 1

protocol

Modbus master, Modbus slave and barcode reader

baud rate

9600, 19200, 38400

connector

SUB-D

external inputs

via the Modbus master/slave function, 24 analog and 24 binary

Ethernet (connector 6)

quantity

max. 1

protocols

TCP, IP, HTTP, DHCP, SMTP, ModbusTCP

baud rate

10 Mbits/sec, 100 Mbits/sec

connector

RJ45

data format

HTML