6 Technical data (extract from data sheet)
36
6.2 Binary inputs/outputs (option)
6.3 Outputs
6.4 Interfaces
Input or output
configurable as input or output
Number
8, 16 or 24, depending on the device version,
to DIN VDE 0411, Part 500; max. 25 Hz, max. 32 V
Input
•
level
logic "0": -3 to +5 V (input current max. ±1 mA),
logic "1": 12 to 30 V (2.5 mA
input current 5 mA)
•
counting frequency
8Hz
High-speed input
the first two binary inputs of each module (B1, B2, B9, B10, B17, B18),
if the module is not fitted with relays or 6 analog inputs
•
task
count function, e.g. for flow measurement
•
counting frequency
10 kHz
Output
•
type
open-collector output, switches relative to positive voltage
•
level
logic "0": transistor is inhibited
(max. permissible voltage across switching transistor 30 V,
max. leakage current 0.1 mA)
logic "1": transistor is switched on
(max. voltage across switching transistor 1.6 V, max. current 50 mA)
•
sampling cycle
at least 1 sec (1 Hz)
1 relay (ex-factory)
changeover (SPDT), 3 A, 230 V AC
a
a
With resistive load.
6 relays (option)
changeover (SPDT), 3 A, 230 V AC
a, b
b
It is not permissible to mix SELV circuits and supply circuits.
RS232/RS485 (connector 7)
Qty. 1, switchable between RS232 and RS485
•
protocol
Modbus master, Modbus slave and barcode reader
•
baud rate
9600, 19200, 38400
•
modem
can be connected
•
connector
SUB-D
•
external inputs
via the Modbus master/slave function, 24 analog and 24 binary
RS232 for barcode reader
(connector 2)
Qty. 1
•
protocol
Modbus master, Modbus slave and barcode reader
•
baud rate
9600, 19200, 38400
•
connector
SUB-D
•
external inputs
via the Modbus master/slave function, 24 analog and 24 binary
Ethernet (connector 6)
•
quantity
max. 1
•
protocols
TCP, IP, HTTP, DHCP, SMTP, ModbusTCP
•
baud rate
10 Mbits/sec, 100 Mbits/sec
•
connector
RJ45
•
data format
HTML