6 Technical data (extract from data sheet)

Input for DC voltage, DC current

Transducer short circuit/break

Basic range

Accuracy

a

a

The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced
with short spans.

Input resistance

-12 to +112 mV
-10 to +210 mV
-1.5 to +11.5 V
-0.12 to +1.12 V
-1.2 to +1.2 V
-11.2 to +11.2 V

±100

V

±240

V

±6 mV
±1 mV
±2 mV
±12 mV

R

E

 1 M

R

E

 470 k

R

E

 470 k

R

E

 470 k

R

E

 470 k

R

E

 470 k

Shortest span

5mV

Range start/end

freely programmable within the limits in 0.01 mV steps

-1.3 to +22 mA
-22 to +22 mA

±20

A

±44

A

burden voltage

 3 V

burden voltage

 3 V

Shortest span

0.5mA

Range start/end

freely programmable within the limits in 0.01 mA steps

Overrange/underrange

according to NAMUR NE 43

Sampling cycle

Channel 1 to 18: 125 ms in total

Input filter

2nd order digital filter; filter constant adjustable from 0 to 10.0 sec

Electrical isolation

see “Electrical data” on page 37 and
“Overview of the electrical isolation” on page 20

Resolution

>14 bit

Short-circuit

a

a

Programmable reaction of device, e.g. triggering alarm

Break

a

Thermocouple

not detected

detected

RTD temperature probe

detected

detected

Resistance transmitter

not detected

detected

Potentiometer

not detected

detected

Voltage

 ±210 mV

not detected

detected

Voltage > ±210 mV

not detected

not detected

Current

not detected

not detected