Screen

Electrical data

RS232 for barcode reader (connector 2)

Qty. 1

protocol

Modbus master, Modbus slave and barcode reader

baud rate

9600, 19200, 38400

connector

SUB-D

external inputs

via the Modbus master/slave function, 24 analog and 24 binary

Ethernet (connector 6)

quantity

max. 1

protocols

TCP, IP, HTTP, DHCP, SMTP, ModbusTCP

baud rate

10 Mbits/sec, 100 Mbits/sec

connector

RJ45

data format

HTML

USB host (connector 5)

quantity

2 (or 1 with stainless steel front),
connector 5 and front connector (not with stainless steel front); no parallel operation

use

for connecting a memory stick

max. current

100 mA

USB device (connector 15)

quantity

2 (or 1 with stainless steel front),
connector 15 and front connector (not with stainless steel front); no parallel operation)

use

for connecting to the (master) computer

Resolution/size

320 × 240 pixels/5.5"

Type/number of colors

TFT color screen/256 colors

Screen refresh rate

> 150 Hz

Brightness setting

adjustable on instrument

Screen saver (switch-off)

through waiting time or control signal

Supply voltage (switch-mode PSU)

AC 100 to 240 V +10/-15%, 48 to 63Hz or AC/DC 20 to 30 V, 48 to 63Hz (ELV)

Electrical safety

to EN 61010, Part 1, August 2002
overvoltage category II, pollution degree 2

Protection class I

terminal for PE conductor

Test voltages (type test)

mains supply circuit to meas. circuit

with AC supply: 2.3 kV/50 Hz, 1 min,
with AC/DC supply: 2.3 kV/50 Hz, 1 min

mains supply circuit to housing
(protective conductor)

with AC supply: 2.3 kV/50 Hz, 1 min,
with AC/DC supply: 2.3 kV/50 Hz, 1 min

measuring current circuits to
measuring current circuit and housing

500 V/50 Hz, 1 min

electrical isolation between analog inputs

up to 30 V AC and 50 V DC

Supply voltage error

< 0.1 % of range span

Power consumption

approx. 40 VA

Data backup

CompactFlash memory card

Electrical connection

mains supply and relays

at rear through pluggable screw terminals, 5.08 mm raster,
max. conductor cross-section

 2.5 mm

2

or 2× 1.5 mm

2

with ferrules

analog and binary inputs

at rear through pluggable screw terminals, 3.81 mm raster,
max. conductor cross-section

 1.5 mm

2