Resistance transmitter and potentiometer

Input for DC voltage, DC current

Cu50
(TC = 4.26*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire
4-wire

-50 to +100 °C
-50 to +200 °C
-50 to +100 °C
-50 to +200 °C

±0.5 °C
±0.9 °C
±0.5 °C
±0.7 °C

250 µA

250 µA

250 µA

250µA

Cu100 GOST 6651-94 A.4
(TC = 4.26*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire
4-wire

-50 to +100 °C
-50 to +200 °C
-50 to +100 °C
-50 to +200 °C

±0.5 °C
±0.9 °C
±0.5 °C
±0.6 °C

250 µA

250 µA

250 µA

250 µA

Connection circuit

2-, 3-, or 4-wire circuit

Shortest span

15 °C

Sensor lead resistance

max. 30 per conductor for 3-wire/4-wire circuit
max. 10 per conductor for 2-wire circuit

Range start/end

freely programmable within the limits, in 0.1 °C steps

Sampling cycle

Channel 1 to 18: 125 ms in total

Input filter

2nd order digital filter; filter constant adjustable from 0 to 10 sec

Electrical isolation

see “Electrical data” on page 5 and
“Overview of the electrical isolation” on page 18

Resolution

> 14 bit

Features

also programmable in °F

a

The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced with short spans.

Designation

Measuring range

Accuracy

1a

a

The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced with short spans.

Measurement current

Resistance transmitter

up to 4000

±4

100 µA

Potentiometer

  

  to 4000 

±400 m

±4

250 µA

100 µA

Connection circuit

resistance transmitter: 3-wire circuit
potentiometer: 2-/3-/4-wire circuit

Shortest span

60

Sensor lead resistance

max. 30 per conductor for 4-wire circuit
max. 10 per conductor for 2-/3-wire circuit

Resistance values

freely programmable within the limits, in 0.1 steps

Sampling cycle

Channel 1 to 18: 125 ms in total

Input filter

2nd order digital filter; filter constant adjustable from 0 to 10.0 sec

Electrical isolation

see “Electrical data” on page 5 and
“Overview of the electrical isolation” on page 18

Resolution

> 14 bit

Basic range

Accuracy

a

Input resistance

-12 to +112 mV
-10 to +210 mV
-1.5 to +11.5 V
-0.12 to +1.12 V
-1.2 to +1.2 V
-11.2 to +11.2 V

±100

V

±240

V

±6 mV
±1 mV
±2 mV
±12 mV

R

E

 1 M

R

E

 470 k

R

E

 470 k

R

E

 470 k

R

E

 470 k

R

E

 470 k

Shortest span

5mV

Range start/end

freely programmable within the limits in 0.01 mV steps

-1.3 to +22 mA
-22 to +22 mA

±20

A

±44

A

burden voltage

 3 V

burden voltage

 3 V

Shortest span

0.5mA

Range start/end

freely programmable within the limits in 0.01 mA steps

Overrange/underrange

according to NAMUR NE 43

Sampling cycle

Channel 1 to 18: 125 ms in total

Designation

Connection circuit

Measuring range

Accuracy

a

Measurement current