Resistance transmitter and potentiometer
Input for DC voltage, DC current
Cu50
(TC = 4.26*10
-3
1/°C)
2/3-wire
2/3-wire
4-wire
4-wire
-50 to +100 °C
-50 to +200 °C
-50 to +100 °C
-50 to +200 °C
±0.5 °C
±0.9 °C
±0.5 °C
±0.7 °C
250 µA
250 µA
250 µA
250µA
Cu100 GOST 6651-94 A.4
(TC = 4.26*10
-3
1/°C)
2/3-wire
2/3-wire
4-wire
4-wire
-50 to +100 °C
-50 to +200 °C
-50 to +100 °C
-50 to +200 °C
±0.5 °C
±0.9 °C
±0.5 °C
±0.6 °C
250 µA
250 µA
250 µA
250 µA
Connection circuit
2-, 3-, or 4-wire circuit
Shortest span
15 °C
Sensor lead resistance
max. 30 per conductor for 3-wire/4-wire circuit
max. 10 per conductor for 2-wire circuit
Range start/end
freely programmable within the limits, in 0.1 °C steps
Sampling cycle
Channel 1 to 18: 125 ms in total
Input filter
2nd order digital filter; filter constant adjustable from 0 to 10 sec
Electrical isolation
see “Electrical data” on page 5 and
“Overview of the electrical isolation” on page 18
Resolution
> 14 bit
Features
also programmable in °F
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced with short spans.
Designation
Measuring range
Accuracy
1a
a
The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced with short spans.
Measurement current
Resistance transmitter
up to 4000
±4
100 µA
Potentiometer
to 4000
±400 m
±4
250 µA
100 µA
Connection circuit
resistance transmitter: 3-wire circuit
potentiometer: 2-/3-/4-wire circuit
Shortest span
60
Sensor lead resistance
max. 30 per conductor for 4-wire circuit
max. 10 per conductor for 2-/3-wire circuit
Resistance values
freely programmable within the limits, in 0.1 steps
Sampling cycle
Channel 1 to 18: 125 ms in total
Input filter
2nd order digital filter; filter constant adjustable from 0 to 10.0 sec
Electrical isolation
see “Electrical data” on page 5 and
“Overview of the electrical isolation” on page 18
Resolution
> 14 bit
Basic range
Accuracy
a
Input resistance
-12 to +112 mV
-10 to +210 mV
-1.5 to +11.5 V
-0.12 to +1.12 V
-1.2 to +1.2 V
-11.2 to +11.2 V
±100
V
±240
V
±6 mV
±1 mV
±2 mV
±12 mV
R
E
1 M
R
E
470 k
R
E
470 k
R
E
470 k
R
E
470 k
R
E
470 k
Shortest span
5mV
Range start/end
freely programmable within the limits in 0.01 mV steps
-1.3 to +22 mA
-22 to +22 mA
±20
A
±44
A
burden voltage
3 V
burden voltage
3 V
Shortest span
0.5mA
Range start/end
freely programmable within the limits in 0.01 mA steps
Overrange/underrange
according to NAMUR NE 43
Sampling cycle
Channel 1 to 18: 125 ms in total
Designation
Connection circuit
Measuring range
Accuracy
a
Measurement current