Technical data

Analog inputs

Thermocouple

Resistance thermometer

Designation

Measuring range

Accuracy

a

a

The linearization accuracy refers to the maximum measuring range. The linearization accuracy is reduced with short spans.

Fe-CuNi L DIN 43710
Fe-CuNi J EN 60584
Cu-CuNi U DIN 43710
Cu-CuNi T EN 60584
NiCr-Ni K EN 60584
NiCr-CuNi E EN 60584
NiCrSi-NiSi N EN 60584
Pt10Rh-Pt S EN 60584
Pt13Rh-Pt R EN 60584
Pt30Rh-Pt6Rh B EN 60584
W3Re/W25Re D
W5Re/W26Re C
W3Re/W26Re
Chromel-copel GOST R 8.585-2001
Chromel-alumel GOST R 8.585-2001
PLII (Platinel II)

-200 to +900 °C
-200 to +1200 °C
-200 to +600 °C
-270 to +400 °C
-200 to +1372 °C
-200 to +1000 °C
-100 to +1300 °C
0 to 1768 °C
0 to 1768 °C
0 to 1820 °C
0 to 2495 °C
0 to 2320 °C
0 to 2400 °C
-200 to +800 °C
-200 to +1372 °C
0 to 1395 °C

±0.1 %
±0.1 % from -100 °C
±0.1 % from -150 °C
±0.1 % from -150 °C
±0.1 % from -80 °C
±0.1 % from -80 °C
±0.1 % from -80 °C
±0.15 %
±0.15 %
±0.15 % from 400 °C
±0.15 % from 500 °C
±0.15 % from 500 °C
±0.15 % from 500 °C
±0.15 % from -80 °C
±0.1 % from -80 °C
±0.15 %

Shortest span

Type L, J, U, T, K, E, N, chromel-alumel, PLII: 100 °C
Type S, R, B, D, C, W3Re/W26Re, chromel-copel: 500 °C

Range start/end

freely programmable within the limits, in 0.1 °C steps

Cold junction

Pt100 internal or thermostat external constant

Cold junction accuracy (internal)

±1 °C

Cold junction temperature (external)

-50 to +150 °C adjustable

Sampling cycle

Channel 1 to 18: 125 ms in total

Input filter

2nd order digital filter; filter constant adjustable from 0 to 10.0 sec

Electrical isolation

see “Electrical data” on page 5 and
“Overview of the electrical isolation” on page 18

Resolution

> 14 bit

Features

also programmable in °F

Designation

Connection circuit

Measuring range

Accuracy

a

Measurement current

Pt100 EN 60751
(TC = 3.85*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire

-200 to +100 °C
-200 to +850 °C
-200 to +850 °C

±0.5 °C
±0.8 °C
±0.5 °C

250 µA

250 µA

250 µA

Pt100 JIS 1604
(TC = 3.917*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire

-200 to +100 °C
-200 to +650 °C
-200 to +650 °C

±0.5 °C
±0.8 °C
±0.5 °C

250 µA

250 µA

250 µA

Pt100 GOST 6651-94 A.1
(TC = 3.91*10

-3

1/°C)

2/3-wire, 4-wire
2/3-wire, 4-wire

-200 to +100 °C
-200 to +850 °C

±0.5 °C
±0.8 °C

250 µA

250 µA

Pt500 EN 60751
(TC = 3.85*10

-3

1/°C)

2/3-wire, 4-wire
2/3-wire, 4-wire

-200 to +100 °C
-200 to +850 °C

±0.5 °C
±0.9 °C

100 µA

100 µA

Pt1000 EN 60751
(TC = 3.85*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire

-200 to +100 °C
-200 to +850 °C
-200 to +850 °C

±0.5 °C
±0.8 °C
±0.5 °C

100 µA

100 µA

100 µA

Ni100 DIN 43760
(TC = 6.18*10

-3

1/°C)

2/3-wire, 4-wire

-60 to +180 °C

±0.4 °C

250 µA

Pt50 ST RGW 1057 1985
(TC = 3.91*10

-3

1/°C)

2/3-wire
2/3-wire
4-wire
4-wire

-200 to +100 °C
-200 to +1100 °C
-200 to +100 °C
-200 to +1100 °C

±0.5 °C
±0.9 °C
±0.5 °C
±0.6 °C

250 µA

250 µA

250 µA

250 µA