2 digital input, 3 digital outputs, Digital outputs – JUMO 705030 mTRON T - Digital Input/Output Module Operating Manual User Manual
Page 26: 4 electrical connection

4 Electrical connection
26
4.3.2
Digital input
The connection depends on the configuration (input or output).
4.3.3
Digital outputs
The connection depends on the configuration (input or output).
Connection
Input
Terminals
Symbol and terminal designation
Apply signal DC 0/24 V to ter-
minals 1 to 12
Ground reference via GND ter-
minal required!
1
2
3
4
5
6
7
8
9
10
11
12
1 and GND
2 and GND
3 and GND
4 and GND
5 and GND
6 and GND
7 and GND
8 and GND
9 and GND
10 and GND
11 and GND
12 and GND
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
GND
Or:
Switch DC 24 V from terminal
+24 V to terminals 1 to 12 via
floating contact.
External voltage supply
DC 24 V via terminals +24 V
and GND required!
1
2
3
4
5
6
7
8
9
10
11
12
1 and +24 V
2 and +24 V
3 and +24 V
4 and +24 V
5 and +24 V
6 and +24 V
7 and +24 V
8 and +24 V
9 and +24 V
10 and +24 V
11 and +24 V
12 and +24 V
+24 V
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
U
+
-
x
Connection
Output
Terminals
Symbol and terminal designation
Output signal:
DC 0/24 V / maximum 500 mA
External voltage supply
DC 24 V via terminals +24 V
and GND required!
1
2
3
4
5
6
7
8
9
10
11
12
1 and GND
2 and GND
3 and GND
4 and GND
5 and GND
6 and GND
7 and GND
8 and GND
9 and GND
10 and GND
11 and GND
12 and GND
1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12
GND
U
+
-
x