1 general data – INFICON BPG402-SP ATM to Ultra-High Vacuum Gauge (Profibus) User Manual
Page 5
![background image](/manuals/562580/5/background.png)
tira47e1 (2005-08) BPG402SPv1.cp
5
1 General Data
The gauge supports all data rates defined in the EN 50170 standard (
→ [5]) up
to 12 Mbaud. Automatic data rate setting is supported. Alternatively, a fixed data
rate can be selected.
The device address (
node address) must be set via two rotary switches when the
gauge is installed.
For unambiguous identification of the gauge in a Profibus environment, a node
address is required. The node address setting is made on the gauge.
The node address (0 … 125
dec
) is set in hexadecimal form
(00 … 7D
hex
) (default value 5C
hex
) via the "ADDRESS" switches.
The "MSD" switch is used for setting the high-order address
nibble and the "LSD" switch for defining the low-order address
nibble.
The node address is polled by the firmware when the gauge is switched on. If the
setting deviates from the stored value, the new value is taken over into the
NVRAM. If a value >7D
hex
(>125
dec
) is entered, the node address setting currently
stored in the device remains valid. However, the address can be set via the
Profibus master with the "Set Slave Address" service. This address setting will be
stored in the EEPROM of the gauge.
The ident number assigned to the gauge by the PNO (
→ [4]) is:
Gauge
Ident number (hexadecimal)
BPG402-SP
0x09AA
Depending on the standard telegrams used (
→ section "Cyclic Message Tele-
grams"), the following configuration data have to be transmitted to the gauge during
the configuration phase:
Standard telegram
Master
⇒ Slave
Standard telegram
Slave
⇒ Master
Configuration data
-
4
0x44, 0x84, 0x05, 0x05, 0x05,
0x03
-
5
0x44, 0x86, 0x05, 0x05, 0x05,
0x08
1
4
0xC6, 0x81, 0x84, 0x05, 0x05,
0x05, 0x05, 0x05, 0x03
1
5
0xC6, 0x81, 0x86, 0x05, 0x05,
0x05, 0x05, 0x05, 0x08
3
6
0xC6, 0x87, 0x8C, 0x0A, 0x0A,
0x05, 0x05, 0x05, 0x03
3
7
0xC6, 0x87, 0x8E, 0x0A, 0x0A,
0x05, 0x05, 0x05, 0x08
2
6
0xC8, 0x89, 0x8C, 0x0A, 0x05,
0x05, 0x0A, 0x05, 0x05, 0x05,
0x03
2
7
0xC8, 0x89, 0x8E, 0x0A, 0x05,
0x05, 0x0A, 0x05, 0x05, 0x05,
0x08
1.1 Data Rate
1.2 Device Address
1.3 Ident Number
1.4 Configuration Data