beautypg.com

Warning – Hydrolevel 3100 User Manual

Page 7

background image

7

YES

Recheck

Wiring.

Replace

Control.

When there is no call to fire the burner, the voltage

should be 0 volts between B1 and B2.

̈ Make sure the burner is wired to B1.

YES

NO

Is the

Low Limit Dial

Set to OFF?

Is there

24 VAC between

B1 and B2?

Is the

Thermostat

(T-TV) Calling

for Heat?

YES

NO

NO

Is the

Red LED

On?

The Control is

Sensing

Low Water.

WARNING!

TURN OFF POWER TO BURNER IMMEDIATELY!

CAUTION – ALWAYS ALLOW A BOILER TO FULLY COOL

BEFORE ADDING WATER.

̈ Recheck wiring. Make sure that burner is wired to

B1. Burner should never fire when red or yellow

LED is lit.

Is the

Yellow LED

On?

The Control is

Sensing High

Temperature.

The Control is

Operating

Normally.

The burner will continue to fire when there is a call

from the thermostat.

̈ Check temperature display. When the Low Limit is

set, the HydroStat will fire the burner until the

temperature reaches the Low Limit Setting.

If there is no call for heat (from T-TV or Low Limit),

there should be 0 VAC between B1-B2.

̈ If there is voltage between B1-B2, the control

should be replaced.

Troubleshooting Flow Chart 2 – Burner Will Not Shut Down

YES

YES

NO

NO