Hydrolevel FS204 User Manual
Warning, Caution, Liquid flow switch
Model FS204
General Purpose
Liquid
Flow Switch
Indoor/Outdoor
•
Universal Design – Replaces
switches by McDonnell & Miller,
Taco, Penn and others
•
Suitable for 1" to 6" Pipe Diameters
•
Adjustable Sensitivity
•
Includes Four Heavy Duty
Stainless Steel Paddles
83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 •
www.hydrolevel.com
FLOW SWITCH LOCATION
DIMENSIONS
The preferred installation of the FS204 is in a horizontal pipe with a straight run of
at least 5 pipe diameters on each side of the paddle (Figure 1). There should be no
restrictions from elbows, valves, orifices, etc. Refer to Table 1 below for flow rates.
The Flow Switch can be installed in a vertical pipe
only if the flow direction of the
liquid is upward.
Table 1 does not apply to vertical installations.
Table 1 FLOW SPECIFICATIONS
Pipe Size
1"
1
1
⁄
4
" 1
1
⁄
2
"
2"
2
1
⁄
2
"
3"
4"
5"
6"
Minimum
Adjustment
Flow
Increases
4.5 8.1 11.8 16.5 25
33
51 85* 120*
Flow
Decreases
2.2 6.8 7.6 9.3 19
22
38 75* 100*
Maximum
Adjustment
Flow
Increases
14.8 22.1 25.7 32.3 75 90* 110* 170* 240*
Flow
Decreases
13.8 20.1 23.7 30.5 72 85* 100* 155* 220*
The Safgard FS204 Flow Switch is used to start or stop electrically
operated equipment such as burners, pumps or alarms by detecting
liquid flow through piping. It is designed for use in water media
applications and is not intended for use in hazardous or corrosive fluids.
The FS204 is suitable for wet locations.
WARNING
Electrical shock hazard.
To prevent electrical shock,
death or equipment damage, disconnect power supply
before installing or servicing control. Only qualified person-
nel may install or service this control in accordance with
local codes and ordinances. Read instructions completely
before proceeding.
CAUTION
• To prevent serious burns, boiler should be
thoroughly cooled before installing or servicing
control.
• The FS204 is designed as an operating control. It is the responsibility of the
installer to provide safety or limit control on installations where an operating
control failure would result in personal injury and/or property loss.
• The FS204 is not intended for use in explosive environments.
FIGURE 1
2.5
3.56
2.2
3.56
2.2
3.34
*Calculated for various pipe sizes. Flow rates may vary ±10% from values above.
Model FS204 Instructions 7/3/12 10:17 AM Page 1