6

NO

NO

Is the

Thermostat

(T-TV) Calling

for Heat?

Is There

24 VAC

Between B1

and B2?

NO

Is the

Low Limit Dial

Set to OFF?

YES

NO

YES

Is the

Red LED

On?

The Control is

Sensing

Low Water.

CAUTION – ALWAYS ALLOW A BOILER TO COOL BEFORE ADDING WATER

The burner will not fire until the low water condition is satisfied.

̈ Check that the system is filled with water.
̈ Check that the sensor is inserted correctly into well.

Note: The use of heat-conductive grease may interfere with the

contact between the spring clip and the copper well tube.

̈ Check that the control is tightly clamped to the well.

Is the

Yellow LED

On?

The Control is

Sensing High

Temperature.

If both the red and yellow LEDs are off and

there is a call to fire the burner, there will be

24 VAC on terminals B1 and B2.

̈ If 24 VAC is not present, the control should

be replaced.

HydroStat is supplying 24 VAC to the burner circuit.

̈ Recheck wiring and operation of burner and other limit controls.

The Control

is Operating

Properly.

Replace

Control

The burner will not fire until the boiler water has dropped to the

high limit differential set-point. See HydroStat Settings chart.

̈ Check that the high temperature setting is correct.

Troubleshooting Flow Chart 1 – Burner Will Not Fire

YES

YES

NO

Is the

Green LED

(TEMP ACTIVE)

On?

The Control is

Not Powered.

The Temp Active LED will be on at all times when the control is

powered.

̈ Check for 120 VAC on terminals L1 and L2.

YES

NO

Is the

Red LED on

the Circuit Board

flashing?

The Load on

the Transformer

Exceeds 30 VA.

The burner will not fire until overload condition is corrected.

̈ Recheck wiring – Terminal TV is electrically connected to boiler

ground. If wiring to TV & Z is reversed, there could be a short

across the transformer.

̈ Make sure that the total load, including the burner circuit, vent

damper and Z & TV connections does not exceed 30 VA.

NO

YES

When the low temperature

setting is set to OFF, the

HydroStat will act as a cold

start control. The burner will

not fire unless there is a call

from the thermostat (T-TV).

̈ Set thermostat to call for

heat. Burner should fire.

̈ If the boiler has a tank-

less coil, set the Low

Temperature Limit to

maintain temperature.

YES