beautypg.com

Hydrolevel 3250 User Manual

Warning, Caution, Three function design

background image

1

83 Water Street • New Haven, CT 06511 • Phone (203) 776-0473 • FAX (203) 773-1019 •

www.hydrolevel.com

MODEL 3250

Temp Limit / LWCO Control

with Thermal Targeting

for Water Boilers

120 VAC Operating Voltage

PATENT NO. 7,891,572

WARNING

Electrical shock hazard. To prevent electrical shock, death or
equipment damage, disconnect power supply before

installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.

CAUTION

To prevent serious

burns, boiler

should be thoroughly cooled before installing or
servicing control.

Three Function
Design

Temperature Limit Control

Designed for cold start and tankless

coil boilers.

Low Water Cut-Off

Provides protection against potentially

dangerous low water conditions

when installed with the Hydrolevel

Electro-Well™ (see page 2 for details).

Boiler Reset Control

Utilizes

Thermal Targeting

technology to conserve fuel by

monitoring heating demand and

establishing target boiler temperatures

below the high limit setting (see page 7

for details).

INSTALLATION INSTRUCTIONS
and OPERATING MANUAL

• Saves Fuel – Features Thermal Targeting™ technology and

Thermal Pre-Purge capability

• Universal Design – Replaces common cold-start and triple-action

Aquastats*

• Easy to Install – Industry standard wiring, dial-type settings,

no external sensors necessary

• Operating Indicators – LEDs, Dynamic Display and Test Button provide

continual and on-demand status checks

• Prioritizes Domestic Hot Water – Gives priority to low limit setting or to

calls from indirect water heater

• Reduces Condensation – Holds circulator off until boiler reaches 120°F

*Aquastat is a registered trademark of Honeywell International, Inc.