Hydrolevel 250 Series User Manual

Typical applications, Warning! 1, Location 2

background image

LOW WATER CUT-OFF

LEVEL INDICATOR

Only qualified personnel may install or service the control
in accordance with local codes and ordinances.
Read instructions completely before proceeding.

WARNING: To prevent electrical shock
and equipment damage, power must
be off during installation or servicing of
the control. To prevent serious burns
the boiler should be thoroughly cooled
before installing or servicing control.

WARNING!

1

Reliable Electronic Design

Made in the U.S.A

No moving parts to stick, wear or hang-up.

No replacement or rebuilding of floats or

mechanical parts.

LISTED

LOCATION

2

Install the Safgard 250 in a
1" equalizing line equipped
with a blow-down valve
meeting applicable state
and local codes. The control
should be located so that
the "LOW WATER CUT-OFF LEVEL” marked on the control casting
is at least 1/2” above the lowest permissible water level as specified
by the boiler manufacturer.

Pump Control Low Water

Cut-Off Combination

120 VAC Operating Voltage

Max. Pressure 250 psi

250 Series

1

2

3

5

INCOMING WATER LINE

4

TYPICAL APPLICATIONS

Safgard 727 Tank Control

Safgard VF-120 Solenoid Valve

1

Safgard 250 Pump Controller LWCO Combination

Safgard 270 High Water Limit/Alarm

3

Safgard 550 or 750 as Secondary LWCO

2

4

5

HOW TO INSTALL