9.4 Sequential analogue output of the CS 1000
The analogue output signal of the measured values is output to
PIN 2 of the CS 1000 to the HDA 5500 sequentially as follows.

Explanation: Output of the sequential analogue output (each 4 .. 20 mA):


Start

signal:

20

mA

2

s

Signal 1:

Measurement ISO4

0 .. 24.4

2 s

Pause (4 mA)

2 s

Signal 2:

Measurement ISO6

0 .. 24.4

2 s

Pause (4 mA)

2 s

Signal 3:

Measurement ISO14

0 .. 24.4

2 s

Pause (4 mA)

2 s

Signal 4:

Measurement ISO21

0 .. 24.4

2 s

Pause (4 mA)

2 s

Signal 5:

Status signal

See table below for the signal

levels used

2 s

Pause before the next output cycle:

4 mA

30 s

Note: the setting ranges must be set in the basic menu.

Status signal

Status display HAD 5500

Condition

Level of status signal

0

CS working smoothly

5 mA

1

Device error / CS not ready

6 mA

2

Flow rate too low

(FLOW 2 LOW)

7 mA

3

Below the measuring limit

(ISO <9. <8. <7)

8 mA

4

No measured value

(Flow undefined)

9 mA

t

Start

Status

Start

20mA

4mA

I

2s

30s

2s

4

µ

m

6

µ

m

14

µ

m

21

µ

m