9.3 Sequential analogue output of the HLB 1000
The analogue output signal of the measured values is output at PIN 4 of the HLB 1000 to the
HDA 5500 sequentially, as follows:

t

Start

Rel.

Visco

Rel.

DC

Rel.

humidity

Temp.

Status

Start

20mA

4mA

I

2s

30s

2s

Explanation: Output of sequential analogue output:
(each 4..20 mA)

O

utput signal

Duration

Start

signal:

20

mA

2

s

Signal 1:

Relative change in the viscosity

-30% ... +30%

2 s

Pause (4 mA)

2 s

Signal 2:

Relative change in the dielectric constant

-30% ... +30%

2 s

Pause (4 mA)

2 s

Signal 3:

Relative humidity

0% ... +100%

2 s

Pause (4 mA)

2 s

Signal

4: Temperature

-25°C...

+100°C

2

s

Pause (4 mA)

2 s

Signal 5:

Status signal

For levels see table below

2 s

Pause before the next cycle:

4 mA

30 s

Status signal

Status display HDA 5500

Status

Level of the status signal

0

Reference phase (no error)

5 mA

1

Function phase (no error)

7 mA

2 or 3

Fluid condition out of range

9 or 11 mA

4 to 7

Internal error

13 to 19 mA

Note:

The exact description of the status signal can be found in the Manual for the HLB 1000.
Due to possible tolerances, we recommend setting the threshold approx. 0.25 mA below the ideal value
given in the table.