DRIVE SPECIFICATIONS AND DIMENSIONS

Model Number

AD052045

AD070059

AD096074

AD096096

AD150145

Input from power
source

Voltage

180 -264 AC (Single or Three Phase)

Frequency

50/60 Hz

Current (Max) - RMS

14.2 Amps 1ø

(6.7 Amps 3ø)

17.4 Amps 1ø

(8.7 Amps 3ø)

23.2 Amps 1ø

(11.9 Amps 3ø)

23.2 Amps 1ø

(11.9 Amps 3ø)

29.5 Amps 1ø

(15.7 Amps 3ø)

Power Factor

1.0 ( constant )

Output to Motor
(Three Phase )

Voltage

Voltage Automatically Adjust with Frequency (0 thru 230 Volts)

Frequency Range

15 - 60 Hz

Current, Factory Programmed*
(RMS, Each Phase)

4.5 Amps

5.9 Amps

7.4 Amps

9.6 Amps

14.5 Amps

Current (Max)
(RMS, Each Phase)

5.2 Amps

7.0 Amps

9.6 Amps

9.6 Amps

15.0 Amps

For Use With

Motor

Standard 60 Hz. Pump & 230 Volt 3 Phase Motor Combination

Reference HP Rating*

1

1.5

2

3

5

Pressure Setting

Factory preset

50 PSI

Adjustable Range

30 - 80 PSI

Operating
Conditions

Temperature
(@ 230 VAC input)

10° to 40° C ( 14° to 104° F. )

Relative Humidity

Max 95% Non-condensing

Controller Size

NEMA 1 ( indoor )

10.47” H x 3.35” W x 6.15” D

12.54” H x 3.94” W x 6.90” D

15.60” x 4.48” x 8.05”

Weight

2.9 lbs.

3.1 lbs.

4.6 lbs.

4.6 lbs.

9.9 lbs.

RMS = ROOT MEAN SQUARED
* The electrical characteristics of motors vary slightly. See Amp draw on motor nameplate. If the maximum motor cur-
rent value (Amp draw) is more than 5% of the programmed value of the Drive, the Drive will need to be set to the
current value of the motor to provide proper protection..

0 1 2 3 4 5 6 7 8

6.0

5.0

4.0

3.0

2.0

1.0

0.0

Run Time (Min.)

Off

Time (Min.)

IL0750

Figure 12

Over-teMPerAture
The Artesian Drive controller is designed for full power opera-
tion in ambient temperatures up to 104°F (40°C) as long as
the input voltage is kept at 230 VAC. Under extreme thermal
conditions, the controller will reduce the switching frequency
in an attempt to avoid shutdown. If the temperature of the
controller is still too hot the controller will shut itself off to

avoid causing damage to itself. Full pump output is restored
when the controller temperature cools to a safe level.
NOTE: The Artesian Drives are factory programmed to
F&W pumps to provide optimum performance and motor
protection. The Artesian Drive can be used with other
pumps, but the maximum motor amperage needs to be
compared to the factory programmed current value (refer
to the Specifications section under the appropriate model).
If the maximum motor current varies more than 5% from
the programmed value, the motor current value in the drive
needs to be changed for motor protection and optimum
performance. For details on how to change this value in the
drive, please contact Technical Support at 1-800-345-9422.