the following procedure:
a. Remove the rubber end-cap.
b. Using a 7/32” Allen wrench (provided), turn the adjusting

screw clockwise to increase pressure and counter-
clockwise to decrease pressure. The adjustment range is
between 30 and 80 psi (1/4 turn = approximately 3 psi).

c. Replace the rubber end cap.
d. Reset the pressure tank pre-charge to the appropriate

pressure.

e. Cover the pressure sensor terminals with the rubber boot

provided.

When increasing the pressure, do not

exceed the mechanical stop on the pressure sensor or 80 psi.
The pressure sensor may be damaged.

NOTE: Ensure that the system is properly grounded all the
way to the service entrance panel. Improper grounding may
result in the loss of voltage surge protection and interference
filtering.
sPeCIAl InstruCtIOns FOr OutDOOr InstAllAtIOn
To install the Artesian Drive in an outdoor installation,
the drive must be placed inside NEMA 3R enclosure (Not
Included).

start-up and Operation

Apply power to the controller. As long as the display is lit up
the system has power. When the display shows  . or

tABle 5: DIAGnOstIC FAult CODes

DIsPlAy CODe

FAult

POssIBle CAuse

COrreCtIve ACtIOn

 

Motor Underload

Air-locked pump. Overpumped
or dry well. Worn pump.
Damaged shaft or coupling.
Pump deadhead. Blocked pump
or screen.

Wait for well to recover and auto-
matic restart timer to time out. If
the problem does not correct, check
motor and pump. See description of
“Intelligent Reset” on Page 18.

 

Undervoltage

Low line voltage. Misconnected
input leads.

Check for loose connections. Check
line voltage. Report low voltage
to the power company. Unit will
start automatically when the proper
power is supplied.

 

.

Locked Pump

Motor/pump misaligned.
Abrasive/Sand-bound pump.
Dragging pump or motor.

Unit will attempt to free a locked
pump. If unsuccessful, check the
motor and pump.

 

.

Short Circuit

When fault is indicated imme-
diately after power-up, short
circuit due to loose connection,
defective cable, splice or motor.

Check motor wiring. Turn power off
till display darkens then apply power
again to reset.

 

.

Over Current

When fault is indicated while
motor is running, over current
due to loose debris trapped
in pump, or water demand is
exceeding pump & motor’s capa-
bility.

Check pump.

 

.

(Number other than

0.0 & motor is not

running)

Open Circuit

Loose connection. Defective
motor or cable.

With power off, check motor, motor
wiring and splices. Make certain all
connections are tight. Apply power
again to reset.

 

.  .

Overheated Controller

High ambient temperature.
Direct sunlight. Obstruction of
air-flow.

This fault automatically resets when
the temperature returns to a safe
level.

 

.

Controller Stopped

Loose jumper wire

Re-insert jumper wire into control
terminals B2 & B4.

DIAGnOstIC FAult CODes
Should an application or system problem occur, built-in diag-
nostics will protect the system. The display will change to
indicate the nature of the fault. In some cases, the system will
shut itself off until corrective action has been taken. Fault

codes and the recommended corrective action for each are
listed in the following chart.

!

Do not attempt to carry out internal
repairs. Return a faulty drive to the

supplier for repair.