Pressure tank – Flint & Walling Artesian Drive Controllers - AD150145 User Manual

Page 4

background image

4

(FW1086)

95 North Oak St. • Kendallville, IN 46755 • 1-800-345-9422

There should be at least 4 inches of

clearance on each side and below the unit to allow room for
air flow.

IL0735

4”

Min

4”

Min

4”

Min

Motor

Pump

Inlet

Pressure Relief

Valve

Tank

Pressure

Sensor

Leads

Pressure Tank to

Pressure Sensor

Mounting

Clearance

Outlet

Power to

Motor

Power Supply from Circuit Breaker

4” Min

6 Ft.

or Less

Figure 3a - Mounting Clearance - Booster Pumps

IL0784

4”

Min

4”

Min

4”

Min

Motor

Pump

Inlet

Pressure Relief

Valve

Tank

Pressure

Sensor

Leads

Pressure Tank to

Pressure Sensor

Outlet

Power to Motor

Power Supply

from Circuit

Breaker

4” Min

6 Ft.

or Less

Figure 3a - Mounting Clearance - Centrifiugal Pumps

4. Do not expose a Artesian Drive to rain or water spray. For

outdoor installations, place the drive inside a NEMA 3R
enclosure. Note: Please reference maxim temperature
ratings listed above.

Correct

Power to

Motor

Pressure

Sensor

Leads

Mounting Orientation

Power

Supply

from Circuit

Breaker

Incorrect

Power

to Motor

Pressure

Sensor

Leads

Power

Supply

from

Circuit

Breaker

IL0734

Figure 4 - Mounting Orientation

5. The Artesian Drive should only be mounted with the wiring

end oriented downward. The controller should not be placed
in direct sunlight or other locations subject to extreme
temperatures or humidity (mounting location should not be
subjected to freezing conditions or condensation).

6. The mounting location should have access to 230 VAC

electrical supply and to the pump motor wiring. To avoid
possible interference with other appliances, please refer to
the enclosed Installation Guide and observe all precautions
regarding power cable routing.

CIrCuIt BreAKer AnD WIre sIzInG
The minimum circuit breaker size and maximum allowable
wire lengths for connection of motor to the Artesian Drive
are given in the following table:

tABle 1: MInIMuM BreAKer sIze AnD MAxIMuM
CABle lenGth (In Feet)

Drive

Model

Recommended

Input Cable

Recommended

Motor Cable

Maximum

Cable

Length to

Motor (Ft.)

Recommended

Breaker

Maximum

Continuous

Current

AD052045

12

16

325

20

5.2

AD070059

12

16

325

25

7.0

AD096074

10

14

325

30

9.6

AD096096

10

14

325

30

9.6

AD150145

8

12

325

30

15.0

A 10-foot section of cable is provided with the Artesian Drive
to connect the pressure sensor.
NOTE:

Maximum allowable wire lengths are measured between
the controller and motor.

Aluminum wires should not be used with the Artesian
Drive.

Wire sizing between the service entrance and the control-
ler must be sufficient to provide the required maximum
input amps to the controller while conforming to local
standards and codes.

Artesian Drive minimum breaker amps may appear to
exceed specifications for the three-phase motor because
Artesian Drive controllers are supplied from a single-
phase service rather than three-phase.

Pressure tank

The Artesian Drive needs only a small pressure tank to main-
tain constant pressure (see table below for recommended