Det-Tronics X3301 Multispectrum IR Flame Detector User Manual
Page 31

29
95-8527
19.2
FM Approval and performance Report – Continued
0°
15°
30°
45°
15°
30°
45°
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)
5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
Field of View at Indicated Distance in Feet (m) for
Methanol at very high Sensitivity (6 in. x 6 in.)
0°
15°
30°
45°
15°
30°
45°
150 (45.7)
135 (41.2
120 (36.5)
105 (32)
90 (27.4)
75 (22.9)
60 (18.3)
45 (13.7)
30 (9.1)
15 (4.6)
Field of View at Indicated Distance in Feet (m) for
Methanol at very high Sensitivity (1 x 1 foot)
Field of View at Indicated Distance in Feet (m) for
Jp-5 at very high Sensitivity (2 x 2 feet)
0°
15°
15°
30°
45°
30°
45°
210
(64)
180 (54.9)
150 (45.7)
120 (36.5)
90 (27.4)
60 (18.3)
30 (9.1)
0°
15°
30°
45°
15°
30°
45°
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
100 (30.5)
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)
10 (3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)
Field of View at Indicated Distance in Feet (m) for
Methane at very high Sensitivity (30 inch plume)
0°
15°
45°
15°
30°
30°
DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45° FROM HORIZONTAL.
0°
15°
15°
30°
45°
30°
45°
210 (64)
180 (54.9)
150 (45.7)
120 (36.5)
90 (27.4)
60 (18.3)
30 (9.1)
30 (9.1)
60 (18.3)
90 (27.4)
120 (36.5)
150 (45.7)
180 (54.9)
210 (64)
Field of View at Indicated Distance in Feet (m) for
Ethanol at very high Sensitivity (1 x 1 foot)