Specifications – Det-Tronics X3301 Multispectrum IR Flame Detector User Manual
Page 19
![background image](/manuals/557666/19/background.png)
17
95-8527
19.2
SPECIfICaTIONS
OPERaTING VOLTaGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm.
4.5 watts at 30 Vdc nominal;
6.5 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power:
17 watts at 30 Vdc with EOL resistor installed
and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8577.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELayS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-
latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open/normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (OPTIONaL)—
0 to 20 milliampere (±0.3 mA) dc current, with a maximum
loop resistance of 500 ohms from 18 to 19.9 Vdc and 600
ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERaTURE RaNGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +125°C.
HUMIDITy RaNGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis. Unlike
conventional detectors, the X3301 provides full coverage
at a minimum of 70% of the maximum detection distance.
Perfect cone of vision for methane fire detection — 100
feet (30.5 m) on and off axis on “very high” setting.
Refer to Appendix A for FM Approved cone of vision data.
RESPONSE TIME—
Typical response times are under 10 seconds. Models
are available that can respond to automotive paint
gun fires in under 0.5 seconds. See Appendix A and
“Automotive Addendum” (95-8534) for actual response
times.
DIMENSIONS—
See Figure 19.
10.0
(25.4)
4.8
(12.2)
4.7
(11.9)
B2067
Figure 19—X3301 Dimensions in Inches (cm)