Det-Tronics X3301 Multispectrum IR Flame Detector User Manual
Page 27

25
95-8527
19.2
FM Approval and performance Report – Continued
FALsE ALARM IMMuNITy
very high sensitivity
False Alarm source
Distance
feet (m)
Modulated Response
unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
40 (12.2)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Medium sensitivity
False Alarm source
Distance
feet (m)
Modulated Response
unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0.3)
No alarm (keyed)
No alarm (steady)
Arc welding
10 (3)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2.4)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
T-Low sensitivity
False Alarm source
Distance
feet (m)
Modulated Response
unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
70 w sodium vapor
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm
Low sensitivity
False Alarm source
Distance
feet (m)
Modulated Response
unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Radio frequency interference
N/A
No alarm
N/A
Arc welding
5 (1.5)
No alarm
No alarm
6 kw heater
3 (0.9)
No alarm
No alarm
250 w vapor lamp
3 (0.9)
No alarm
No alarm
300 w incandescent lamp
3 (0.9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0.9)
No alarm
No alarm
1500 w electric radiant heater
3 (0.9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0.9)
No alarm
No alarm