Det-Tronics X3301 Multispectrum IR Flame Detector User Manual
Page 18
![background image](/manuals/557666/18/background.png)
95-8527
16
19.2
X3301 Reflector plates
X3301 models are supplied with either a black or a
stainless steel reflector plate. These plates are not
interchangeable. Order the replacement that matches
the reflector plate on your X3301 Flame Detector.
pERIODIC ChECkOuT pROCEDuRE
In compliance with SIL 2, a checkout of the system
using the Mag
oi
or Man
oi
feature should performed
regularly to ensure that the system is operating properly.
Refer to Table 1 in the X3301 Safety manual (95-8582) for
frequency of proof tests. To test the system, perform the
“Fire Alarm Test” as described in the “Startup Procedure”
section of this manual.
CLOCk BATTERy
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
fEaTURES
• Long detection range to carbonaceous fires
• Unequaled false alarm rejection
• Responds to a fire in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm
• Microprocessor controlled heated optics for increased
resistance to moisture and ice
• Automatic, manual, or magnetic
oi
testing
• Easily replaceable
oi
plate
• Fire, fault and auxiliary relays standard
• 0 to 20 mA isolated output (optional)
• Eagle Quantum Premier LON/SLC output (optional)
• HART communication (optional)
• FDT/DTM capable
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
• Operates under adverse weather conditions and in
dirty environments
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of installation
• Explosion-proof/flame-proof detector housing.
Meets FM, CSA, ATEX Directive and CE certification
requirements
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under 0.5
second (available when model selected)
• 5 year warranty
• RFI and EMC Directive compliant
Associated Manuals
List of X3301 related manuals:
TITLE
FORM NuMBER
Pulse
95-8528
EQP
95-8533
SIL 2 (Safety)
95-8582
HART Addendum
95-8577
Automotive Addendum
95-8534
Hangar
95-8548
Q9033 Mounting Arm
and Collar Attachment
95-8686
Inspector Monitor Software for
X-Series Flame Detectors
95-8581
Q1130 Flange Mount
95-8662