95-8527

16

19.2

X3301 Reflector plates
X3301 models are supplied with either a black or a

stainless steel reflector plate. These plates are not

interchangeable. Order the replacement that matches

the reflector plate on your X3301 Flame Detector.

pERIODIC ChECkOuT pROCEDuRE
In compliance with SIL 2, a checkout of the system

using the Mag

oi

or Man

oi

feature should performed

regularly to ensure that the system is operating properly.

Refer to Table 1 in the X3301 Safety manual (95-8582) for

frequency of proof tests. To test the system, perform the

“Fire Alarm Test” as described in the “Startup Procedure”

section of this manual.

CLOCk BATTERy
The real time clock has a backup battery that will

operate the clock with no external power. Return the

device to the factory for battery replacement if needed.

NOTE

If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.

fEaTURES

• Long detection range to carbonaceous fires
• Unequaled false alarm rejection
• Responds to a fire in the presence of modulated

blackbody radiation (i.e. heaters, ovens, turbines)

without false alarm

• Microprocessor controlled heated optics for increased

resistance to moisture and ice

• Automatic, manual, or magnetic

oi

testing

• Easily replaceable

oi

plate

• Fire, fault and auxiliary relays standard
• 0 to 20 mA isolated output (optional)
• Eagle Quantum Premier LON/SLC output (optional)
• HART communication (optional)
• FDT/DTM capable
• Multiple sensitivity levels
• A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm

or fault conditions

• Operates under adverse weather conditions and in

dirty environments

• Mounting arm allows easy sighting
• Integral wiring compartment for ease of installation
• Explosion-proof/flame-proof detector housing.

Meets FM, CSA, ATEX Directive and CE certification

requirements

• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under 0.5

second (available when model selected)

• 5 year warranty
• RFI and EMC Directive compliant

Associated Manuals
List of X3301 related manuals:

TITLE

FORM NuMBER

Pulse

95-8528

EQP

95-8533

SIL 2 (Safety)

95-8582

HART Addendum

95-8577

Automotive Addendum

95-8534

Hangar

95-8548

Q9033 Mounting Arm

and Collar Attachment

95-8686

Inspector Monitor Software for

X-Series Flame Detectors

95-8581

Q1130 Flange Mount

95-8662