OUTpUTS
Relays
The detector is furnished with fire and fault relays. The

relays are rated 5 amperes at 30 Vdc.

The Fire Alarm relay has redundant terminals and normally

open / normally closed contacts, normally de-energized

operation, and latching or non-latching operation.

The Fault relay has redundant terminals and normally

open contacts, normally energized operation, and

latching or non-latching operation.

Latching relays can be reset by removing input power

(0.1 second minimum).

An alarm condition will normally over-ride a fault condition,

unless the nature of the fault condition impairs the ability

of the detector to generate or maintain an alarm output,

i.e. loss of operating power.

LED
A tri-color LED on the detector faceplate indicates

normal condition and notifies personnel of fire alarm

or fault conditions. Table 1 indicates the condition of the

LED for each status.

oi

(OpTICaL INTEgRITy)

automatic

oi

The X5200 includes the Automatic oi feature — a

calibrated performance test that is automatically

performed once per minute to verify complete detector

operation capabilities. No testing with an external test

lamp is required. The detector automatically performs

the same test that a maintenance person with a test

lamp would perform — once every minute. However, a

successful Automatic oi test does not produce an alarm

condition.

The X5200 signals a fault condition when less than half

of the detection range remains. This is indicated by the

fault relay and is evident by the yellow color of the LED

on the face of the detector. See the “Troubleshooting”

section for further information.

Magnetic

oi / Manual oi

CaUtIon

These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.

The detector incorporates both Magnetic oi (Mag oi)

and Manual oi (Man oi) test capabilities. These tests

provide pulses (80 to 100 CPS) to the controller (R7404

or R7494) when the detector is not in fault. If the test

is successful, the controller indicates a fire and the

appropriate zone output is active.

NOTE

If the detector is in a fault condition, a successful
Mag

oi

or Man

oi

test cannot be performed.

Table 1—Detector Status Indicator

Detector Status

LED Indicator

Power On/Normal Auto

oi

(no fault or fire alarm)

Green

Power On/Normal Man

oi

Green, flashing on for

0.5 sec. every 0.5 sec.

Fault

Yellow

UV Alarm only

Red, flashing on for 5 sec.

and off for 5 sec.

IR Alarm only

Red, flashing on for 0.25 sec.

and off for 0.25 sec.

Pre-Alarm

Red, flashing on for 1 sec.

and off for 1 sec.

Fire (Alarm)

Steady Red

On Power-Up, The LED Flashes in Sequence as Follows,

Indicating Sensitivity and Signal Processing Status

Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity

One Red Flash

Two Red Flashes

Three Red Flashes

Four Red Flashes

Stand. UV Signal Process.
Arc Rej. UV Signal Process.

One Yellow Flash

Two Yellow Flashes

Low IR Sensitivity
Medium IR Sensitivity
High IR Sensitivity
Very High IR Sensitivity

One Green Flash

Two Green Flashes

Three Green Flashes

Four Green Flashes

Quick Fire/TDSA IR Signal
TDSA only IR Signal
Quick Fire only

One Yellow Flash

Two Yellow Flashes

Three Yellow Flashes