Det-Tronics X5200 UVIR Flame Detector with Pulse Output User Manual
Page 19
17
95-8547
7.1
3. Press the SELECT button until the desired zone is
displayed on the ZONE indicator on the controller
front panel.
4. Press and hold the TEST button. The DETECTOR/
ZONE display indicates the counts per second (cps)
received from the detector. If the counts per second
exceeds 99, the FIRE LOGIC LEDs are illuminated to
indicate that the number shown on the display must
be multiplied by 10. The normal reading for an oi
test is 80 to 110 cps. For a live fire test, 270 - 330
cps will be generated.
A zero reading may indicate a dirty window, oi problem,
faulty detector or defective wiring.
Release the TEST button, the ZONE and DETECTOR
display should drop to a reading of 0 to 1 counts per
second.
FIRE aLaRM TEST (pulse Output to Fire alarm panel)
1. Disable any extinguishing equipment that is
connected to the system.
2. Apply input power to the system.
3. Initiate a live fire test or a Mag oi test. (See
“Magnetic oi / Manual oi” under “Optical Integrity”
in the Description section of this manual.)
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (Det-Tronics’
Q1201C Laser Aimer is recommended for this
purpose.)
6. Enable extinguishing equipment when the test is
complete.
TROUBlESHOOTINg
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
3. Check input power to the unit.
4. Check system and detector logs.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check
for high levels of background UV or IR radiation
by covering the detector with the factory supplied
cover or aluminum foil. If the fault condition clears,
extreme background UV or IR radiation is present.
Re-adjust the view of the detector away from the UV
or IR source or relocate the detector.
If none of these actions corrects the problem, return the
detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.