Det-Tronics X5200 UVIR Flame Detector with Pulse Output User Manual
Page 20
95-8547
7.1
18
maINTENaNCE
Important
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
WarnIng
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X5200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
CLEaNINg pROCEDURE
CaUtIon
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and oi plate, use Det-Tronics
window cleaner (p/n 001680-001) and a soft cloth, cotton
swab or tissue and refer to the following procedure:
1. Disable any extinguishing equipment that is
connected to the unit.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
2. Clean the viewing window and reflective surfaces
of the oi plate using a clean cloth, cotton swab or
tissue, and Det-Tronics window cleaning solution.
Use Isopropyl alcohol for contaminations that
the Det-Tronics window cleaning solution can not
remove. If a fault condition is still indicated after
cleaning, remove and clean the oi plate using the
oi
Plate Removal and Replacement procedure.
Important
When used in extreme environments, the reflective
surface of the detector
oi
plate may eventually
deteriorate, resulting in reoccurring
oi
faults and
the need for
oi
plate replacement.
oi
pLaTE REMOVaL aND REpLaCEMENT
1. Disable any extinguishing equipment that is
connected to the unit.
2. Loosen the two captive screws, then grasp the
oi
plate by the visor and remove it from the detector.
See Figure 14.
3. Install the new (or cleaned) oi plate.
4. Recalibrate the detector’s oi system. Refer to the
Inspector Monitor Manual (95-8581) for instructions
regarding oi plate replacement and oi system
recalibration.
CaUtIon
Do not replace the
oi
reflector plate without also
recalibrating the
oi
system.
Recalibration of the oi system requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
pERIODIC CHECKOUT pROCEDURE
A checkout of the system using the Mag oi or Man oi
feature should be performed on a regularly scheduled
basis to ensure that the system is operating properly. To
test the system, perform the “Manual oi Test,” “Count Test
Mode” or “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
CLOCK BaTTERy
The real time clock has a backup battery that will operate
the clock with no external power for nominally 10 years.
It is recommended that the battery be replaced every
7 years. Return the device to the factory for battery
replacement.
figure 14—
oi
Plate Removal
LOOSEN TWO CAPTIVE SCREWS
GRASP VISOR AND
REMOVE
oi PLATE
C2135