beautypg.com

Det-Tronics X5200 UVIR Flame Detector with Pulse Output User Manual

Page 26

background image

95-8547

7.1

24

FM approval and performance Report – Continued

Very High Sensitivity UV & IR, Low arc, TDSa On, Quick Fire On

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

85 (25.9)

14

Methane

32 inch plume

65 (19.8)

5

High Sensitivity UV, Very High Sensitivity IR, Hi arc, TDSa On, Quick Fire Off

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

60 (18.3)

6

Methane

32 inch plume

65 (19.8)

9

Medium Sensitivity UV, High Sensitivity IR, Hi arc, TDSa On, Quick Fire On

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

5

Methane

32 inch plume

60 (18.3)

5

High Sensitivity UV & IR, Very Hi arc, TDSa On, Quick Fire On

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

8

High Sensitivity UV, Low Sens. IR, Hi arc, TDSa On, Quick Fire Off

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

15 (4.6)

9

High Sensitivity UV, Very High Sens. IR, arc Off, TDSa On, Quick Fire On

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

Methane

32 inch plume

15 (4.6)

0.12

High Sensitivity UV, Very High Sens. IR, Hi arc, TDSa On, Quick Fire On

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

Methane 32 inch plume

15 (4.6)

0.3

RESpONSE CHaRaCTERISTICS

High Sensitivity UV & IR, Hi arc, TDSa On, Quick Fire Off

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

7

Methane

32 inch plume

35 (10.7)

3.5

High Sensitivity UV & IR, Very Hi arc, TDSa On, Quick Fire Off

Fuel

Size

Distance feet (m)

Typical Response Time (seconds)

n-Heptane

1 x 1 foot

50 (15.2)

8