Figures 11 and 12 provide examples of typical

installations with a X5200 wired to a fire alarm

panel.
Figure 13 shows an EOL resistor installed within the

integral wiring compartment of the detector (refer to

“EOL Resistors” for details).

2. Check all field wiring to be sure that the proper

connections have been made.

Important

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.

3. Make the final sighting adjustments and use a 14 mm

hex wrench to ensure that the mounting arm assembly

is tight.

13.1

(33.4)

10.6

(27.0)

4.0

(10.2)

4.0

(10.2)

3.0

(7.6)

3.0

(7.6)

4X ø0.42

(1.1)

E2069

NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.

figure 3—Q9033 mounting arm without Collar attachment Dimensions in Inches (cm)

(See figure 1 for Correct Detector Orientation .)

figure 5—X5200 Pulse Wiring Terminal Identification

figure 4—X5200 Terminal block

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE

COM FIRE

N.O. FIRE

N.O. FIRE

N.C. FIRE

N.C. FIRE

COM FAULT

COM FAULT

N.O. FAULT

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

B2070