beautypg.com

Det-Tronics X5200 UVIR Flame Detector with Pulse Output User Manual

Page 22

background image

95-8547

7.1

20

CONE Of VISION—

The detector has a 90° cone of vision (horizontal) with

the highest sensitivity lying along the central axis.

See Figure 15.

RESPONSE TImE—

32 inch methane plume: < 10 seconds.

1 foot x 1 foot n-Heptane: < 15 seconds.

(See Appendix A for details.)

ENCLOSURE maTERIaL—

Copper-free aluminum (painted) or Stainless Steel (316/

CF8M Cast).

VIbRaTION—

Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).

DImENSIONS—

See Figure 16.

WIRINg—

Field wiring screw terminals are UL/CSA rated for up to

14 AWG wire, and are DIN/VDE rated for 2.5 mm

2

wire.

Screw terminal required torque range is 3.5–4.4 in.-lbs.

(0.4-0.5 N·m).
Important:

18 Vdc minimum must be available at the

detector. For ambient temperatures below –10°C (14°F)

and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.

ThREaD SIZE—

Conduit connection: Four entries, 3/4 inch NPT or M25.

Conduit seal not required.

ShIPPINg WEIghT (approximate)—

Aluminum:

7 pounds (3.2 kilograms).

Stainless Steel:

14.6 pounds (6.7 kilograms).

Mounting Arm (AL): 6 pounds (2.75 kilograms).

Mounting Arm (SS): 14 pounds (6.4 kilograms).

WaRRaNTy PERIOD—
3 years.

CERTIfICaTION—

FM

APPROVED

®

VdS

For complete approval details, refer to the appropriate

Appendix:

Appendix A - FM

Appendix B - CSA

Appendix C - ATEX/CE

Appendix D - IECEx

Appendix E - EN54

Appendix F - Additional approvals

10.2

(25.9)

4.8

(12.2)

4.7

(11.9)

B2223

figure 16—Dimensions in Inches (cm)

0°

15°

30°

45°

15°

30°

45°

VIEWING ANGLE

A1288

100

90

80

70

60

50

40

30

20

10

DETECTION

DISTANCE

(PERCENT)

100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A

GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF

INCIDENCE DECREASES.

figure 15—Detector Cone of Vision