Appendix c, Atex / ce approval – Det-Tronics NTMOS IP66/IP67 H2S Gas Detector User Manual
Page 17
![background image](/manuals/557582/17/background.png)
2.1
95-8670
15
APPENDIX C
ATEX / CE APPROVAL
NOTE
The NTMOS Gas Detector is designed and approved as a ‘stand alone’ toxic gas detector.
Hazardous Location
ATEX: 0539
FM
APPROVED
®
II
2
G
Ex
d
IIC
T5
Gb
FM09ATEX0063X
T5
(Tamb=
–40°C
to
+65°C)
IP66/IP67 (with hydrophobic filter and sinter guard)
IP63
(without
hydrophobic filter).
EN
Standards:
EN
50270:
2006
EN
60079-0:
2009
EN
60079-1:
2007
EN 60529: 1991+ A1 2000.
IECEx:
Ex
d
IIC
T5
Gb
IECEx
FMG
09.0011X
T5
(Tamb=
–40°C
to
+65°C)
IP66/IP67 (with hydrophobic filter and sinter guard)
IP63
(without
hydrophobic filter).
IEC
Standards:
IEC
60079-0:
2007
IEC 60079-1: 2007
IEC 60529: 2001
Special Conditions for Safe Use (X) / Schedule of Limitations:
• The NTMOS Hydrogen Sulfide Toxic Gas Detector shall be connected directly to a junction box or instrument
suitable for the area of installation to provide protection for the flying leads.
• The NTMOS Hydrogen Sulfide Toxic Gas Detector, when the optional sinter guard is not fitted, meets the impact
test requirements according to the low level risk of mechanical danger. Therefore, when the optional guard is not
fitted, the NTMOS Hydrogen Sulfide Toxic Gas Detector must be located and installed such that the risk of impact
is reduced.
• In order to maintain IP66/IP67 Ingress Protection rating, the detector must be mounted vertically at a maximum
height of 18 inches from surfaces below.