Despatch/Watlow 1500 Control Instruction Manual

Page 33

Ecosphere Sample Profile Worksheet

Program Name

Date

Step

No.

Set Point

Events

Duration

Comments

CH-1

E

C or

E

F

S1

CH-2

% or

E

S2

1 = ON

E1

4321

0 = OFF

E2

4321

HR

MN

SC

1

25

95

0001

0000

00

10

00

Initialize system at ambient.

2

40

--

0001

--

00

30

00

Ramp to 40

E

C in 30 minutes.

3

--

--

--

--

00

30

00

Hold for 30 minutes.

4

25

--

--

--

00

30

00

Ramp to 25

E

C in 30 minutes.

5

--

--

--

--

00

30

00

Hold 25

E

C for 30 minutes.

6

10

--

0001

--

00

00

01

Step Ramp to -10. Humid event OFF.

7

W1 (-8)

--

--

--

--

Wait for -8

E

C. ALL OTHER W'S BLANK.

8

--

--

--

--

00

30

00

Hold -10 for 30 minutes.

9

JS02

JC01

Jump to step 2. Repeat once.

10

25

40

0001

--

00

00

01

Return to ambient with low humidity.

11

SP

SP = Blank step. End of program.

12

13

NOTE:
--'s indicate blanks, which are not the same as 00's. To get
blank in data display, press the FCTN key instead of the
ENTER key.