Despatch/Watlow 1500 Control Instruction Manual

Page 31

E1 = Event 1:

4

3

2

1

> Power Devices

0

Off

1

On

> Cooling Fan

0

Off

1

On

> Nitrogen (optional)

0

Off

1

On

> Ramp/Test Light

0

On

1

Off

E2 = Event 2:

4

3

2

1

> Autofill

0

Off

1

On

> Heaters

0

Off

1

On

> Vent Solenoid

0

Open

1

Closed

> Drain Solenoid

0

Closed

1

Open

HAST Chamber Programming Instructions and
Definitions

C1 = Channel 1, Temperature (

E

C)

C2 = Channel 2, Relative Humidity (%RH)

SP = Set Points
S1 = Set Temperature
S2 = Set Relative Humidity

WT = Wait Loop
WE = Wait Event:

1 = Wait for Temperature
2

= Wait for Relative Humidity

3

= Wait for Water Level

4

= Wait for Water Temperature

JL

= Jump Loop

JS

= Jump to Step

JC

= Number of Times to Perform Jump

NX = Next Programming Step