beautypg.com

Creating files/profiles – Despatch 1500 Controller User Manual

Page 22

background image

Page 16

Despatch/Watlow 1500 Control Instruction Manual

Creating Files/Profiles

See sections on “SAMPLE HAST PROFILE” and
“PROCEDURE FOR PROGRAMMING HAST PROFILE” for
LPB chambers.

1.

Press the MODE key to select the CHANGE DATA
mode. The FUNCTION display will indicate one of three
submodes:

SP-Set Point,

JL-Jump Loop,

WT-Wait.

2.

Press the FCTN key until SP appears in the function
display.

3.

Press the ENTER key. S1 will appear in the
FUNCTION display and 0000 will appear in the DATA
display.

4.

Use the FCTN key to select the variable to edit. See
the example on Table 7, Channel 1 (S1).

5.

Enter a set point for the channel selected in step 4.

a. Use the

>

key and the

?

key to change the value in

the DATA display.

OR

Use the FCTN key to advance to the next prompt
without entering a value.

b. Press the ENTER key to enter the value in the DATA