Operation – Carbolite TZF Series User Manual
Page 5
STF/TZF
MF08 – 3.24
5
3.0 O
PERATION
The instructions for operating the temperature controller are given in a separate manual.
If the furnace is fitted with a time switch, see also the supplementary manual MS03.
If cascade control is fitted, see the supplementary manual MS07.
3.1 Operating Cycle (STF models)
The furnace is fitted with an instrument switch. The switch cuts off power to the control circuit.
There is also a heater switch which can be used to disconnect power to the elements.
Connect the furnace to the electrical supply.
Operate the instrument switch to activate the temperature controller. The controller becomes
illuminated and goes through a short test cycle.
Adjust the temperature controller (see controller manual).
Overtemperature option only. If the overtemperature controller has not yet been set as required, set
it and activate it according to the instructions in the appropriate manual.
Unless a time switch is fitted and is off, the furnace starts to heat up. The Heat light(s) glow
steadily at first and then flash as the furnace approaches the desired temperature or a program
setpoint.
Overtemperature option only. If the overtemperature trip operates then an indicator in the
overtemperature controller flashes, and the heating elements are isolated. Find and correct the
cause before resetting the overtemperature controller according the instructions supplied.
To turn the furnace off, set the Instrument switch to it’s off position; the controller display will go
blank. If the furnace is to be left off unattended, isolate it the electrical supply.
3.2 Operating Cycle (TZF models)
See section 3.3 for a description of the control methods A, B & C.
The furnace is fitted with a combined Supply light and Instrument switch. The light is on
whenever the furnace is connected to the supply. The switch cuts off power to the control circuit.
Connect the furnace to the electrical supply. The Supply light should glow.
Operate the instrument switch to activate the temperature controller. The controller becomes
illuminated and goes through a short test cycle.
Control methods A & B: Set the slave (end zone) controllers to the desired offset temperature,
usually zero. Set the main (central) temperature controller to the desired setpoint or program. See
section 3.3 and the separate manual(s) for the controller(s).
Control method C: Set the three controllers to the desired temperatures. See the separate
manual(s) for the controller(s).
Overtemperature option only. If the overtemperature controller has not yet been set as required, set
it and activate it according to the instructions in the appropriate manual.
Unless a time switch is fitted and is off, the furnace starts to heat up. The Heat light(s) glow
steadily at first, then flash as the furnace approaches the desired temperature or a program setpoint.
Overtemperature option only. If the overtemperature trip operates then an indicator in the
overtemperature controller flashes, and the heating elements are isolated. Find and correct the
cause before resetting the overtemperature controller according the instructions supplied.
To turn the furnace off, set the Instrument switch to it’s off position; the controller display will go
blank. If the furnace is to be left off unattended, isolate it the electrical supply.