beautypg.com

Programming, Perational – Class1 Total System Manager User Manual

Page 5

background image

5

SWITCH SOURCES

Ignition

Loads will sequence on when

the vehicle ignition switch is turned ON.

Warning Master

Loads will sequence on when

the master warning switch is
turned ON.

EACH

LOAD

CAN

BE

PROGRAMMED

FOR

ACTIVATION

BY

EITHER

SOURCE

OUTPUT MODES

Response Mode

Output is ON only when the
Park Brake is

NOT set.

Scene Mode

Output is ON only when the
Park Brake

IS set.

Both

Output is ON in both Response
and Scene Mode.

EACH

LOAD

CAN

BE

PROGRAMMED

FOR

RESPONSE

MODE

,

SCENE

MODE

,

OR

BOTH

.

O

PERATIONAL

D

ATA

OPERATING VOLTAGE

7.5 to 20 Volts D.C.

OUTPUTS

High Side Drivers Vmain at 0.5 amp.

(source)

Low Side Driver

Ground at 0.5 amp.

(sink)

TRANSIENT SUPPRESSION

Outputs are protected against thermal
overload, direct shorts and transient
spikes from -50 to +60 volts D.C.

OVERRIDE

Outputs 1 through 12 are forced on when the override switch is active.

AUXILIARY BATTERY MONITORING

Terminal #23 can be used to monitor an
auxiliary battery. There should be no con-
nection to this terminal if a remote battery
is not monitored. If the auxiliary battery
voltage drops below 11.9 volts, it will acti-
vate the auxiliary battery low output.

Twelve (12) outputs can be programmed by the user to be activated by the Ignition or
Master Switch, tied to Scene Mode, Response Mode or Both, and assigned a Specific
Priority Level. More than one output load can be set to the same Priority Level.

USER SETPOINT/VARIABLE TRIP

This is the user definable output. The user
has the option of selecting a ‘trip’ voltage
between 10.5 and 15.0 VDC. If the trip
point is set to 13.8 V or above, the output
acts as an overvoltage indicator and will
‘energize’ when the selected voltage is
reached. If the ‘trip’ point is set below
13.8 VDC, then the output will ‘energize’
when the voltage drops to the setpoint.