Default settings, Efault, Ettings – Class1 Total System Manager User Manual
Page 12
12
D
EFAULT
S
ETTINGS
PRIORITY SHED POINT UNSHED POINT
8
12.7
13.0
7
12.6
12.8
6
12.4
12.6
5
12.2
12.4
4
12.0
12.2
3
11.8
12.0
2
11.4
11.6
1
11.0
11.4
Loads 9 through 12 are set to priority zero and come on with the ignition
switch.
These loads will sequence on and off but will not shed due to low voltage.
Loads 1 through 12 are configured to BOTH modes, scene and response.
Load #13 is the User Configurable Output.
The default setting for this ‘Variable Trip’ Point is 14.5 VDC.
Load #14 is the AUXILIARY Battery Alarm.
Load #15 is the Fast Idle Output.
This load becomes active when the system voltage drops to 12.8 VDC.
Load #16 is the Low Voltage Alarm Output.
This load becomes active when the system voltage drops below 11.9 VDC.
Parking Brake and Master Switch Input Jumpers are set to ground (-).
The factory default settings can be reprogrammed into the system by pressing and
holding the ‘
USER
’ and ‘
PRG
’ switches for fifteen (15) seconds, (
dEF
) will be shown
on the display panel when the defaults have been reprogrammed.
Loads 1 through 8 are set to priority 1
through 8 respectively and are tied to the
Master Warning Switch.
These loads will sequence on 1 through 8
and sequence off 8 through 1. They will
shed 8 through 1 when the system volt-
age falls to the shed point for that priority
level.
The Total System Manager is shipped with the following default settings.
manuals\TSM\TSM_MNL1.pm6-052097
NOTE
: On some units the user switch is labeled var trip!