PRIORITY SHED POINT UNSHED POINT

8

12.7

13.0

7

12.6

12.8

6

12.4

12.6

5

12.2

12.4

4

12.0

12.2

3

11.8

12.0

2

11.4

11.6

1

11.0

11.4

Loads 9 through 12 are set to priority zero and come on with the ignition
switch.
These loads will sequence on and off but will not shed due to low voltage.

Loads 1 through 12 are configured to BOTH modes, scene and response.

Load #13 is the User Configurable Output.
The default setting for this ‘Variable Trip’ Point is 14.5 VDC.

Load #14 is the AUXILIARY Battery Alarm.

Load #15 is the Fast Idle Output.
This load becomes active when the system voltage drops to 12.8 VDC.

Load #16 is the Low Voltage Alarm Output.
This load becomes active when the system voltage drops below 11.9 VDC.

Parking Brake and Master Switch Input Jumpers are set to ground (-).

The factory default settings can be reprogrammed into the system by pressing and
holding the ‘

USER

’ and ‘

PRG

’ switches for fifteen (15) seconds, (

dEF

) will be shown

on the display panel when the defaults have been reprogrammed.

Loads 1 through 8 are set to priority 1
through 8 respectively and are tied to the
Master Warning Switch.

These loads will sequence on 1 through 8
and sequence off 8 through 1. They will
shed 8 through 1 when the system volt-
age falls to the shed point for that priority
level.

The Total System Manager is shipped with the following default settings.

manuals\TSM\TSM_MNL1.pm6-052097

NOTE

: On some units the user switch is labeled var trip!