If the installation requires draining the condensate water away
from the unit, install a 2-in. trap at the condensate connection to
ensure proper drainage. See Fig. 9. Make sure that the outlet of the
trap is at least 1 in. lower than the drain pan condensate connection
to prevent the pan from overflowing. Prime the trap with water.
Connect a drain tube using a minimum of 3/4 -in. PVC or 3/4 -in.
copper pipe (all field-supplied) at the outlet end of the 2-in. trap.
Do not undersize the tube. Pitch the drain tube downward at a
slope of at least one in. for every 10 ft of horizontal run. Be sure
to check the drain tube for leaks.

VII.

INSTALL FLUE HOOD

The flue hood assembly is shipped screwed to the coil panel in the
indoor blower compartment. Remove the service access panel to
locate the assembly.

CAUTION: The venting system is designed to ensure
proper venting. The flue hood assembly must be installed
as indicated in this section of the unit installation instruc-
tions.

NOTE: Dedicated low NO

x

models MUST be installed in Cali-

fornia Air Quality Management Districts where a Low NO

x

rule

exists.

These models meet the California maximum oxides of nitrogen
(NO

x

) emissions requirements of 40 nanograms/joule or less as

shipped from the factory.

NOTE: Low NO

x

requirements apply only to natural gas instal-

lations.

Install the flue hood as follows:

1. This installation must conform with local building codes

and with the National Fuel Gas Code (NFGC), ANSI
Z223.1 (in Canada, CAN/CGA B149.1, and B149.2) or
NFPA (National Fire Protection Association) latest revi-
sion. Refer to Provincial and local plumbing or waste water
codes and other applicable local codes.

2. Remove flue hood from shipping location (inside the

blower compartment). Place vent cap assembly over flue
panel. Orient screw holes in vent cap with holes in the flue
panel.

Fig. 8—Suggested Rigging

A05179

UNIT 583B

SIZE

MAXIMUM WEIGHT

A

B

lb

kg

in.

mm

in.

mm

030

335

152

22.0

558.5

15.3

388.6

036

343

156

22.0

558.5

15.3

388.6

042

404

183

23.0

584.2

16.3

414.0

048

443

201

21.5

546.1

16.3

414.0

060

490

222

23.5

596.9

16.3

414.3

DETAIL A

Fig. 9—Condensate Trap

C99013

1” (25mm) MIN.

2” (50mm) MIN.

TRAP
OUTLET

Fig. 10—Sediment Trap

C99020

OUT

TEE

NIPPLE

CAP

IN

3˝ MIN

—7—