Fig. 6—583B030, 036 Unit Dimensions

C99017

UNIT

ELECTRICAL

CHARACTERISTICS

UNIT WEIGHT

UNIT HEIGHT

IN. (MM)

"A"

CENTER OF GRAVITY

IN. (MM)

lb.

kg.

X

Y

Z

583B030040/060

208/230-3-60

313.0

142.0

39.02 (991.1)

22.0 (558.8)

15.3 (387.4)

17.6 (447.0)

583B036060/090

208/230-3-60,

460-3-60

321.0

145.6

35.02 (889.5)

22.0 (558.8)

15.3 (387.4)

16.5 (419.1)

REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)

Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts

. . . . . . . . . . . . . . . . . . . . . 36 (914)

Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*

*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall

system, then the system performance may be compromised.

REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)

Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)

Flue Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 (914.4)

NEC REQ’D CLEARANCES. in. (mm)

Between units, power entry side

. . . . . . . . . . . . . . 42 (1066.8)

Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side

. . . . . . . . . . . . . . . . . 42 (1066.8)

LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)

—5—