Bryant R-410A 583B User Manual
Page 5
Fig. 6—583B030, 036 Unit Dimensions
C99017
UNIT
ELECTRICAL
CHARACTERISTICS
UNIT WEIGHT
UNIT HEIGHT
IN. (MM)
"A"
CENTER OF GRAVITY
IN. (MM)
lb.
kg.
X
Y
Z
583B030040/060
208/230-3-60
313.0
142.0
39.02 (991.1)
22.0 (558.8)
15.3 (387.4)
17.6 (447.0)
583B036060/090
208/230-3-60,
460-3-60
321.0
145.6
35.02 (889.5)
22.0 (558.8)
15.3 (387.4)
16.5 (419.1)
REQ’D CLEARANCES FOR OPERATION AND SERVICING. in. (mm)
Evaporator coil access side . . . . . . . . . . . . . . . . . . 36 (914)
Power entry side (except for NEC requirements) . . . . . . . . . 36 (914)
Unit top . . . . . . . . . . . . . . . . . . . . . . . . . . 48 (1219)
Side opposite ducts
. . . . . . . . . . . . . . . . . . . . . 36 (914)
Duct panel . . . . . . . . . . . . . . . . . . . . . . . . 12 (304.8)*
*Minimum distances: If unit is placed less than 12 in. (304.8 mm) from wall
system, then the system performance may be compromised.
REQ’D CLEARANCES TO COMBUSTIBLE MAT’L. in. (mm)
Top of unit . . . . . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Duct side of unit . . . . . . . . . . . . . . . . . . . . . . . 2 (50.8)
Side opposite ducts . . . . . . . . . . . . . . . . . . . . . 14 (355.6)
Bottom of unit . . . . . . . . . . . . . . . . . . . . . . . 0.50 (12.7)
Flue Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36 (914.4)
NEC REQ’D CLEARANCES. in. (mm)
Between units, power entry side
. . . . . . . . . . . . . . 42 (1066.8)
Unit and ungrounded surfaces, power entry side . . . . . . . . . 36 (914)
Unit and block or concrete walls and other grounded
surfaces, control box side
. . . . . . . . . . . . . . . . . 42 (1066.8)
LEGEND
CG - Center of Gravity
COND - Condenser
EVAP - Evaporator
NEC - National Electrical Code
REQ'D - Required
Note: Dimensions are in in. (mm)
—5—